When connecting to a DuplineSafe
Safety Relay Output module directly or
to a Safety Input module through the
Adapt 7380, configuration mode is
enabled. This is done automatically
when activating the unit where the text
“Configurator

mode

selected!”

is

shown shortly in the display, followed
by the text “Config Unit begin?”. Now
pressing the “Read / On” or the “Yes”
button will start the reading of the con-
nected unit, “Reading Configuration” is
shown in the display while reading is in
progress.

Output Unit:

If a Safety Relay Output module is
connected the following screen will
now be shown:

Here the number of channels selected
on the Dupline channel generator must
be entered. Press ”No” to change,
press ”Yes” to approve and continue.
The next thing to do is selecting the
channels where Safety Input modules
are placed. The following screen is
shown on the display (Note. In Grp.A
channels 1 and 2 are not selectable):

The black numbers show that a Safety
Input is selected for these channels.
The ordinary big numbers show that
the channels are not used. To change
channels 1,2 use button “1” or “2”. To
change
channels 3,4 use button “3” or ”4”,
channels 5,6 use button “5” or “6”,
channels 7,8 use Button “7” or “8”.
Use button “No” to go back and but-
ton “Yes” to approve. Selecting Safety
Inputs must be done for all used
Dupline groups.

Next, the synchronization channel
must be entered.

Press

“No”

to

change

Sync

channel and “Yes” to approve. The let-
ters on the Configuration and Test Unit
buttons works just like on a cell phone
(e.g. press 3 times on button “2” to get
an “F”).

Next, you must enter whether the cur-
rently connected Safety Relay Output
module should generate the sync
channel, or if it should just listen to a
sync channel generated by another
Safety Relay Output module.

Press the button “1” for Yes and the
button “2” for No. Press the button
“No” to go back and press the button
“Yes” to approve.

Finally, enter if the Output unit should
use Automatic or Manual restart.

Press the button “1” for Yes and the
button “2” for No. Press the button
“No” to go back and press the button
“Yes” to approve.

Now the following text will appear:
“Send data to unit?

Yes / No”. Press

button “Yes” to send the entered con-
figuration to the connected Safety
Relay Output module. Press “No” to
reenter the configuration data.

Input Unit:

If a Safety Input module is connected
through the ADAPT 7380, the following
screen will be shown:

As shown, a cursor will start at the first
letter. Enter the letter required. The let-
ters on the Configuration and Test Unit
buttons work just like on a cell phone
(e.g. press 3 times on button “2” to get
an “F”). Press “Yes” to go forward and
press “No” to go back.

When done, the following text will
appear: “Send data to unit?

Yes /

No”. Press button “Yes” to send the
entered configuration to the connected
Safety Input module. Press “No” to
reenter the configuration data.

Test Unit mode

When connecting to a DuplineSafe
bus, the Test Unit mode is entered.
When activating the unit as described
above the text “GTU mode selected!”
is shown shortly on the display, fol-

lowed by the text “Enter Sync. Chan-
nel: A1”.
Here the Sync. Channel used in the
connected DuplineSafe system must
be entered. Press the “No” button to
change the Sync. Channel, or press
the “Yes” button to use the default A1
channel.
When the “Yes” button is pressed, the
GTU unit will try to lock on to the
Sync. Channel. During this operation,
the words “Please Wait.!

Locking

Sync.*” will be shown in the display.

If the sync. Channel is found, the text
“Sync. Channel Locked to:

xx” (xx is

the channel entered) will be shown in
the display, or else “Sync. Channel Not
Found!” will be displayed, and the
Sync. Channel can be reentered.

If the Sync. Channel is OK, the top line
in the display will show “UNITS ON
GROUP.A” and the bottom line will
show the current state of the Safety
Input modules on group A:

Explanation of symbols used in the
bottom line:
1. “S”: The Sync. Channel is placed on
this Dupline channel.
2. “--“ The Channels are unused.
3. Ordinary numbers, e.g “34”: An
Input unit is placed on these channels
and it’s not activated.
4. Darkened numbers, e.g “

”:

An Input unit is placed on these chan-
nels and it’s activated.

Press button “Yes” to go to the next
group or press “No” to go to the previ-
ous group.

Low Battery

If, when activating the Configuration
and Test Unit, “ * LOW BATTERY * ” is
showed in the display, it is time for
changing the battery. The unit will con-
tinue to work, but it is recommended
that the battery is changed. The bat-
tery is changed by dismounting the 4
screws on the back of the unit and
removing the back cover. After that,
take out the PCB, change the 9V bat-
tery and then reassemble the unit.

Configuration Mode

GS73800080