Configurations

Carlin EZ-Temp components are available in the following configurations, allowing use 
with existing wells in addition to EZ-Temp wells.
Surface-mount sensors are also available.

• 

Control kits

 

EZ-Temp controls mount to a standard 4x4 J-box or can be panel mounted. 

Control kits include the control and sensor(s) (item 2) plus hardware needed 

for mounting to an existing well (items 10 and 11). To obtain an EZ-Temp well 

and hardware, obtain an EZ-Temp well kit, below.

• 

Well kits

 

EZ-Temp wells are available in the sizes shown below. Well kits include a 

well (item 1), rubber sensor retainer (item 3), retainer washer (item 4), jam 

nut (item 5), and J-box lock washer (item 8).

• 

Sensor Kits

 

Sensor kits include only the sensor (item 2). Sensors are available in single 

and dual configurations (two sensors in the same assembly). For controls 

that use multiple sensors, obtain separate sensor kits or a sensor kit and a 

dual sensor.

Install sensor(s)

To install a new immersion well:

1.  Turn off power to the appliance and close isolation valves.
2.  Follow appliance instructions to drain the appliance so water line is below 

the insertion tapping.

3.  Remove existing well and sensor. Apply a small amount of pipe dope to the 

new well and secure in tapping.

4.  Insert EZ-Temp sensor into well and secure sensor in place as described in 

the following.

5.  Refill appliance with water, following appliance manual procedures.

  When  routing  sensor  wires,  avoid  sharp  edges  and  use  strain 

relief bushings at penetrations to prevent movement or electrical 
shorting of the sensor. Sensor wires are not low voltage, and must 
be routed in conduit.

Configuration A: Sensor and well only

1.  Insert the sensor into well (1) until the sensor (2) tip bottoms in the well 

socket.

2.  EZ-Temp well: Slide the rubber retainer (3) over the sensor wires until it 

firmly contacts the sensor casing. Slide the retainer washer (4) and the jam 

nut (5) over the wires. Thread the jam nut into the well until snug.

3.  Existing well: Press the sensor retainer plug (11) into the well until it securely 

holds the sensor wires, to prevent movement of the sensor.

Configuration B: Sensor, EZ-Temp well and J-box

1.  Insert the sensor into well (1) until the sensor (2) tip bottoms in the well 

socket.

2.  Slide the rubber retainer (3) over the sensor wires until it firmly contacts the 

sensor casing. Slide the retainer washer (4) over the wires.

3.  Slide the lock washer (8), J-box (7), and jam nut (4) over the wires.
4.  Thread the jam nut into the well and tighten to secure the J-box and sensor 

in place.

Configuration C: Sensor, EZ-Temp well and J-box

1.  Insert the sensor into well (1) until the sensor (2) tip botoms in the well 

socket.

2.  Slide the J-box (7) over the wires and secure the J-box in place by snapping 

the retainer ring (10) onto the well shoulder.

3.  Press the sensor retainer plug (11) into the well until it securely holds the 

sensor wires, to prevent movement of the sensor.

Mount the control

1.  Insert sensor wire terminals into the labelled openings on the back of the 

control. Press into place firmly.

2.  Attach the control to the 4x4 J-box or panel mount, as desired.

Wire the control

1.  Control  wiring  (including  sensor  wires)  must  be  routed  through  conduit 

or  electrical  enclosures.  Follow  all  applicable  codes  and  the  appliance 

manual.

2.  Follow the burner and appliance wiring diagrams to connect the control(s) 

into the appliance limit circuit.

3.  For specific applications, contact your Carlin supplier for further informa-

tion.

Set the control

1.  Follow the appliance manual to set the correct limit temperature for the 

appliance. To adjust the EZ-Temp control:
•  Insert a screwdriver into the setting slot and rotate until the indicator points 

to the desired temperature.

2.  Test the operation of the appliance and the new limit control(s) to verify 

correct operation.

3.  NOTE: EZ-Temp controls have a subtractive differential — control contacts 

trigger when the temperature setting is reached. Contacts reset after tem-

perature drops below setpoint minus the differential amount.