Carlin 702CRD Installation And Operating Instructions Manual Download Page 4

4

OPERATION
1.  Call for heat. Burner motor and ignition are energized. 

Air is in the low-fire position. The low-fire oil valve ad-

mits oil at 100 psi to the nozzle and its spray ignites, 

burning clean with proper air/fuel ratio.

2.  If demand exceeds low-fire, the damper motor 

is energized through a high-fire operating control 

(aquastat, airstat, pressuretrol, or outdoor thermo-

stat). As the damper motor approaches a half open 

position, the auxiliary end switch energizes the high-

fire valve on the fuel unit, closing the by-pass port, 

and increasing the nozzle pressure to 300 psi. Thus 

the full fire with open air burns clean with high CO

2

 

and high efficiency.

3.  As the high-fire input begins to exceed the demand of 

the high-fire operator, the operating control de-ener-

gizes the damper motor. As the damper motor returns 

the air shutter to low-fire, the auxiliary end switch in 

the damper motor de-energizes the high-fire valve 

which drops the nozzle pressure to 100 psi.

4.  If the demand exceeds low-fire, the high-fire operat-

ing control would again call for more heat as in Step 2 

and then Step 3.

5.  If, after returning to low-fire, the load should drop to 

below the low-fire output, the operating limit would 

shut off the burner completely.

It is important that the installation of the oil burner, 

piping and fittings, safety devices, controls, elec-

trical wiring and equipment be done in accordance 

with national and/or local regulations of the author-

ities having jurisdiction over such installation.

If adjustment to the damper motor is needed, please 

reference the included supplement (Part# MNSQN71) 

for all settings and operation.

NOZZLE SPECIFICATIONS
The 60° P Hago nozzle is the standard nozzle and usu-

ally provides the best fire. Substitutions are sometimes 

recommended in specific packaged boilers.
Following is a list of nozzle specifications for packaged 

boilers presently using the 702CRD burner:

Burnham Series V907 - V910: 70° B, Delavan
Burnham Series V911: 60° PLP Monarch
H. B. Smith Series 18: 9-11 Section, 45° P Hago
H. B. Smith Series 19: 7-11 Section, 60° P Hago
Weil-McLain 488, 488R: 60° PLP Monarch
Weil-McLain 588: 70° P Hago.

Other makes of nozzles may or may not prove satisfac-

tory.
For special applications, other specifications might pro-

vide a more desirable pattern.

FORCED DRAFT FIRING
Due to the back pressure in forced draft units, the max-

imum firing rate of a burner is reduced. The greater the 

pressure, the lower the maximum GPH capability  

 

becomes. Table 4 shows this. Note that the Table stops 

at 0.70 inches W.C., the maximum recommended back 

pressure for the 702CRD burner.
The combustion head settings for forced draft firing 

would be somewhat greater than those shown in Table 3 

which is for zero pressure or natural draft.

*

* The “low-fire” pump pressures shown are recommended. If higher low-fire 

inputs are desired for a given situation, the low-fire pressure can be increased 

only up to 200 PSI. Higher low-fire pressures will require higher low-fire air 

openings.

** The “high-fire” pressure is set at the factory to 300 psi. This is the maximum 

UL rating for the fuel unit, so higher pressures are not recommended.

HOW TO ADJUST THE COMBUSTION HEAD
The retention ring position ahead of the throttle ring is 

adjustable from zero (flush) to 1

1

4

 inches (Dimension  

Figures 7 and 8). Turning the adjusting screw (clock-

wise) increases the distance “A” ahead. This distance 

is indicated by llfting the housing cover and reading 

the scale on the nozzle line across the corners on sides 

of the channel guiding the nozzle line. Each division is 

1/16- inch.
Refer to “A” dimension (Table 3) for corresponding 

nozzle selection. Example: 702CRD burner firing at 6.80 

GPH high-lire setting, Column “A” reads 1/8-inch.

TABLE 3 

NOZZLE DATA AND COMBUSTION  

HEAD SETTINGS

Nozzle

Size

Low

Fire

Pres.*

Low

FIre

Rate

GPH

Heat

Setting

“A”

(inch)

Low 

Fire “X”

Air

Open (inch)

High

Fire

Pres.**

High

Fire

Rate

3.50

100

3.50

0

3/8

300

5.95

3.75

100

3.75

1/16

3/8

300

6.38

4.00

100

4.00

1/8

3/8

300

6.80

4.50

100

4.50

3/16

3/8

300

7.65

5.00

100

5.00

1/4

3/8

300

8.50

5.50

100

5.50

5/16

3/8

300

9.35

6.00

100

6.00

7/16

7/16

300

10.20

6.50

100

6.50

5/8

7/16

300

11.05

7.00

100

7.00

7/8

1/2

300

11.90

7.50

100

7.50

1

1

4

1/2

300

12.75

TABLE 4

MAXIMUM FIRING RATES (GPH) – FORCED DRAFT

Summary of Contents for 702CRD

Page 1: ...ort 800 989 2275 carlincombustion com Carlin Combustion Technology Inc The model 702CRD burner is designed to fire No 2 fuel oil and is a low high low off step modulating high speed flame retention bu...

Page 2: ...mes about 30 cfm of air per 1 GPH input To ensure an adequate air supply provi sion must be made for 30 cfm per 1 GPH plus 50 o additional for draft regulator Example Burner is firing at 6 00 GPH 6 X...

Page 3: ...0 14 21 7 65 27 15 0 7 5 15 25 8 50 32 15 5 8 0 15 30 9 35 34 16 0 8 0 16 32 10 20 35 16 0 8 0 16 33 11 05 37 16 5 8 5 16 35 11 90 48 16 5 8 5 16 46 12 75 55 16 5 8 5 16 53 Note These are minimum dim...

Page 4: ...go H B Smith Series 19 7 11 Section 60 P Hago Weil McLain 488 488R 60 PLP Monarch Weil McLain 588 70 P Hago Other makes of nozzles may or may not prove satisfac tory For special applications other spe...

Page 5: ...Normally a draft of 0 02 to 0 04 inches W C negative pressure is recom mended over the fire for natural draft applications Adjust the combustion head only while In high fire The burner is provided wi...

Page 6: ...evel of the burner and the fuel unit must pull lift the fuel up to the burner The vacuum reading should not exceed 12 mercury For two pipe installa tions the by pass plug must be installed Table 5 sho...

Page 7: ...e energized earlier if during the swing the fire gets very smoky then cleans up again the high fire valve should be energized later To adjust the damper end switch remove the damper motor cover This w...

Page 8: ...on Technology Inc T E C H S U P P O R T H O T L I N E 8 0 0 9 8 9 2 2 7 5 Carlin Combustion Technology Inc 126 Bailey Road North Haven CT 06473 Phone 203 680 9401 Fax 203 764 1714 e mail us at info ca...

Reviews: