Carlin 601CRD Installation And Operating Instructions Manual Download Page 6

6

Light-Off and Adjustment

Before re-starting the burner, preset the air shutter and 
the retention ring position for the particular firing rate 
according to Table 2, page 5.
Adjust draft to 0.02 to 0.04 inches W. C. over the fire for 
natural draft units. 
Run a smoke test. Strive for zero or a trace. Each time 

further adjustment of air or retention ring is made, reset 
the draft to 0.02 to 0.04 inches W.C. over the fire.
Check C0

2

. This should be set between 11% and 12%.  

Check for good ignition and clean cut-off. If cut-off 
continues to be poor, look for air leaks in the suction 
line and correct them.

Forced Draft Firing

Due to the back pressure in forced draft units the 
maximum firing rate of a burner is reduced. The greater 
the pressure, the lower the maximum GPH capability 
becomes. Note that the graph at the right stops at 0.30 
inches W.C. for Model 601CRD; the maximum recom-
mended back pressure for this model.
The combustion head settings for forced draft firing 
would be somewhat greater than those shown in Table 
2, page 5, which are for zero pressure or natural draft.

MN00000  111017

© Copyright 2018 — Carlin Combustion Technology, Inc.

T E C H       S U P P O R T       H O T L I N E    8 0 0 - 9 8 9 - 2 2 7 5

Carlin Combustion Technology, Inc.

126 Bailey Road          North Haven, CT 06473        Phone   203–680–9401       Fax   203–764–1714
e-mail us at: 

[email protected]      

visit our website: 

www.carlincombustion.com

Fuel Units and Oil Lines

Standard burners are provided with a two-stage  
3450 rpm fuel unit set at 150 psi.
single-pipe system is recommended whenever the 
bottom of the fuel tank is above the burner or is at the 
same level as the burner. This includes outdoor fuel 
tanks that are at such levels. 
two-pipe system is recommended when the fuel tank 
is below the level of the burner, and the fuel unit must 
pull (lift) the fuel up to the burner. For two-pipe instal-
lations, the by-pass plug must be installed. Maximum 
recommended vacuum is 12 inches of mercury. 
Table 3 shows, for the standard two-stage fuel unit, the 
allowable lift and lengths of 1/2" and 5/8" OD tubing for 
both suction and return lines in two-pipe systems.
Be sure that all oil line connections are absolutely 
airtight. Check all connections and joints. Flared fittings 

are recommended. 

Do not use compression fittings 

or teflon tape. 
Open the air-bleed valve and start the burner. For clean 
bleed, slip a 3/16" ID hose over the end of the bleed 
valve and bleed into a container. Continue to bleed 
for 15 seconds after oil is free of air bubbles. Stop the 
burner and close the bleed valve.

Table 3.  Two-Stage Units – Two Pipe Systems

Lift 

(feet)

Length of Tubing (feet)

1/2" OD                         5/8" OD

  0

  2

  4

  6

  8

10

12

14

15

100

  88

  78

  69

  59

  49

  39

  29

  24

100

100

100

100

100

100

100

  82

  68

Reviews: