background image

MN801GAS  060520

– 10 –

Inspect components and wiring

•  Visually inspect all burner components and wiring.

•  Verify that wiring is intact and leads are securely connected.

•  Verify that all burner components are in good condition.

Install gas train on burner

1.  The standard burner gas train is shipped fully assembled, with the piping 

disconnected at the gas train unions. See separate instructions if installing 

an optional knocked down gas train. The gas train is available in either 

an angled (standard) or straight (optional) configuration.

2.  Connect the main and pilot gas trains at the unions (Figure 4).

  To avoid damage to gas train components, do not hold compo-

nents with a pipe wrench or overtighten. Use only a crescent 

wrench or other means. Failure to comply could result in severe 

personal injury, death or substantial property damage.

3.  Connect the flexible conduit, pre-attached to the burner J-box, to the gas 

train J-box, and attach the wires to the terminal strip inside the gas train 

J-box.

a. 

Match wire colors of the incoming wires to those pre-wired to the terminal 

strip inside the gas train J-box.

b. 

See the label in the burner junction box or the wiring diagrams on pages 

13- 14.

  Gas valve vent opening — The V48 diaphragm gas valve is 

NOT fitted with a vent limiting orifice in the vent connection. 

If local codes require, install piping from the vent connection 

to outside, sized and installed as required by codes. Because 

this is a diaphragm-assisted solenoid valve, a small amount of 

gas will exit from the vent orifice each time the valve opens.

Figure 4 

Gas train installation (shown with angled gas train)

2.  Prepare site  •  assemble burner  •  mount burner 

(continued)

  Connect from the gas supply to the burner gas train inlet using new, clean black iron pipe and malleable iron fittings only. Do not use 

copper, brass, cast iron or galvanized pipe or fittings. 

 

Provide support for gas piping. Do not rest the weight of the gas piping on burner gas train.

 

Provide a support for the burner gas train.

 

Apply pipe dope sparingly at all joints. Use only pipe dope listed for use with propane gas. Do not use pipe sealing tape.

 

Do not hold the gas valve with pipe wrench. Use crescent wrench or other smooth-jawed device. Do not overtighten. 

 

Failure to comply with above could result in severe personal injury, death or substantial property damage.

  Do not expose the gas train to gas pressure in excess of 14 inches water column. Higher pressure could damage the valve seat, 

resulting in potentially hazardous condition. When pressure testing piping at higher pressures, disconnect burner from gas line before 

testing.

 

If the gas supply pressure can exceed 14 inches water column at any time, you must install a lockup type gas pressure regulator in 

the gas supply piping, ahead of the main manual gas valve installed at the burner.

Connect pilot gas 
train at union

Connect main gas 
train at union

Summary of Contents for 52600A

Page 1: ...for information regarding operation of this burner The burner Instruction Manual is intended only for your service technician The burner and heat exchanger must be inspected and started at least an n...

Page 2: ...staller service technician Read all instructions before proceeding Perform all procedures and in the order given to avoid potential of severe personal injury death or substantial property damage Befor...

Page 3: ...tic Gas Conversion Burners ANSI Z21 8 National Fuel Gas Code ANSI Z223 1 NFPA 54 National Electrical Code ANSI NFPA 70 All additional applicable national state and local codes The 801GAS burner config...

Page 4: ...t reaches the combustion zone Firing rate adjustment Gas flow is adjusted to match the air flow at low and high fire rates High fire must be set before low fire See the Starting and operating section...

Page 5: ...eck codes standards and the equipment manual Verify that the burner appliance will maintain all clearances to combustible walls or floor and all clearances required for service maintenance as required...

Page 6: ...used must be no smaller than inch mesh Motorized vent dampers Wire the vent damper end switch to prevent operation of the burner until the air opening louvers are fully open Combustion air ventilatio...

Page 7: ...y could result in severe personal injury death or substantial property damage Prepare burner and components Do not install or operate the burner if any component is dam aged or if burner does not comp...

Page 8: ...sh the same 6 When converting coal fired units install a combustion chamber in the ashpit area or fill the ashpit with sand up to 2 inches above the mud ring of the boiler firing through the door Inst...

Page 9: ...opening so the end of the air tube is flush with or slightly short of the inside surface of the combustion chamber 3 Place gasket onto boiler front plate 4 Slide the end of the air tube into the openi...

Page 10: ...from the vent connection to outside sized and installed as required by codes Because this is a diaphragm assisted solenoid valve a small amount of gas will exit from the vent orifice each time the val...

Page 11: ...You will find additional infor mation on gas line sizing in the National Fuel Gas Code ANSI Z223 1 7 Gas supply pressure natural gas or propane Maximum supply pressure 14 inches w c Minimum supply pre...

Page 12: ...e cubic feet gas hour Figure 6 Gas train pressure drop 3 Install gas piping continued Regulator spring The standard main gas pressure regulator spring 1 RV81 is plated The range is from 3 0 to 6 0 inc...

Page 13: ...ion for burner equipped with a primary control not covered in this manual see Figure 7 for a legend to callouts 4 Wire the burner RM7897C primary control continued Turn off power to appliance when ser...

Page 14: ...steam boiler activated Read the appliance manual for the location of the high fire control when used 3 See Figures 8 and 9A to connect the high fire control to the burner firing rate circuit 4 The bur...

Page 15: ...nt system Are voltages correct Burner appliance and motor correctly wired per burner and appliance manuals and wiring diagrams Gas manifold spud orifices sealed with pipe dope and tight Burner nozzle...

Page 16: ...sted Take your time and the burner should operate properly and you will avoid return service calls You must perform the adjustments in the sequence given in this manual Failure to follow the correct p...

Page 17: ...tep 1 Check gas pilot operation The Model 801GAS uses a gas pilot for ignition of the gas main flame The gas pilot is ignited by the pilot electrode 1 Make sure the gas line has been completely bled T...

Page 18: ...elector switch to OFF The burner will shut down 5 Temporarily install two U tube manometer connections to check gas pres sures Install connections at the inlet pressure tap of the main manual gas valv...

Page 19: ...ckouts force latch up to occur as well Reset primary control per control data sheet instructions after each test Start and stop the burner several times allowing the primary control to sequence throug...

Page 20: ...functioning correctly and that the burner is properly adjusted Failure to comply could result in severe personal injury death or substantial property damage General maintenance Cleaning blower wheel 1...

Page 21: ...Btuh Manifold gas pressure IWC High fire Low fire Inlet gas pressure IWC CO2 Gas Low Fire ______ Gas High Fire ______ Gas Low Fire ______ Gas High Fire ______ O2 Were limit controls tested Comments a...

Page 22: ...MN801GAS 060520 22 9 Dimensions Figure 14 Dimensional data...

Page 23: ...MN801GAS 060520 23 Figure 19 Dimensional data angled gas train configuration 9 Dimensions continued...

Page 24: ...7S Damper Motor SQN71 6 51376S Pilot ignitor 7 28548S Blower Wheel Fan 7 OD x 5 W 5 8 Bore 28555S Blower Wheel Fan 7 5 8 OD x 5 W 5 8 Bore 8 56812S Retention Ring Assy 801CRD 9 35824S Motor Contactor...

Page 25: ...MN801GAS 060520 25 10 Repair parts continued For parts not shown or listed contact factory and or check separate documentation supplied with appliance burner unit...

Page 26: ...onal injury death or substantial property damage Copyright 2020 Carlin Combustion Technology Tech support 800 989 2275 carlincombustion com MODEL SQN71 Damper Actuator Supplement Quick Reference Guide...

Page 27: ...ire Blue Cam Replacing Cover Before putting on the actuator cover be sure the disengaging pin has been engaged CAM INDICATION Cam Color Position Settings 701CRD 702CRD 801CRD 1050FFD 1150FFD 702GO 702...

Page 28: ...and liquids Do not obstruct the flow of combustion and ventilating air Most motors currently used on com mercial type burners use permanently lubricated bearings and do not require field lubrication...

Reviews: