background image

Model 301GAS burner — Instruction manual

Carlin part number MN301GAS Rev. 11/24/14

– 12 –

Where appliance instructions differ from this manual, follow the appliance instructions.

4.  Check system   •   start-up burner/appliance

Inspect/check system

Before starting the burner and appliance, verify the system has been 

installed as directed by this manual and the appliance instructions.

Check gas piping for leaks

  Disconnect the burner from the gas supply line if gas line 

test pressure will exceed 14 inches w.c. Exposing the burner 

gas train to pressure higher than 14 inches w.c. can damage 

the valve seat, resulting in potentially unsafe operation.

You can usually test the gas piping by allowing the line to fill with gas to 

main regulator outlet pressure. 
1.  Shut off gas flow to all equipment connected to the meter.
2.  If test pressure will be less than 14 inches w.c., close the gas train 

manual gas valve. If test pressure will be higher than 14 inches, 

remove the burner gas train from the gas line by shutting off the 

main manual gas valve installed near the burner (per Figure 10, 

page 10) and disconnecting the ground joint union. See WARNING 

above.

3.  Watch the gas meter dial. For a one half cubic foot per revolution dial, 

there should be no movement of the dial for at least 5 minutes. For 

larger volumes per revolution, increase this time proportionately.

4.  If you detect a gas leak, locate the leak with a soap suds mixture and 

repair it. Then test the system for leaks again.

  Do not test for leaks with an open flame. And do not use 

oxygen as a test gas. Either of these could cause an explo-

sion, resulting in severe personal injury, death or substantial 

property damage.

Bleed gas line

Purge all air from the gas line. Purge to outside of the building, NEVER 

into the appliance or burner.

Leak test near-burner gas piping

If piping near burner has not already been pressure tested, open main 

manual gas valve on supply to burner and smell around area for any signs 

of gas. Apply a soap suds mixture to all gas piping joints near burner 

and check for any leaks. If any leaks appear, repair before proceeding 

Figure 12   

Air band adjustment

and retest.

Set burner air band

See Figure 12. Loosen air band locking screw. Then rotate band until it is 

open to the setting given in Table 1 page 7. Tighten air band locking screw.
The Table 1 setting will probably be satisfactory without change. If the 

combustion test indicates a need for more or less air, however, you will 

have to adjust the band accordingly.

Check burner and primary control

Inspect burner thoroughly. Verify that hinged ignitor cover plate is closed 

and screw is tight. Verify all wiring is in place and all components are 

secure and in position.

  Do not start the burner if you smell gas or if there may be gas 

present in the appliance combustion chamber, appliance or 

the vent system. An explosion could occur,  causing severe 

personal injury, death or substantial property damage. 

  During initial start-up, you must be constantly alert for emer-

gency conditions such as fuel leaks, electrical malfunctions, 

etc. Familiarize yourself with the location of manual shutoff 

valves and switches so you can quickly use them if needed.

  If the burner fails to ignite, NEVER attempt to manually 

bypass the normal sequence of the control, which provides 

purging of the combustion chamber. 

Verify flame failure Lockout of 60200FR control

1.  Install a hose barb fitting in the manual gas valve pressure tap (item 

10a, page 3) and connect with a hose to a U-tube manometer.

2.  Close the main manual gas valve and turn the combination gas valve 

knob to ON.

3.  Turn on power to appliance and set appliance limit(s) to call for heat.
4.  Burner motor will start. The 60200FR will run for its prepurge timing, 

then start the ignitor. Approximately one second later, the gas valves 

will open. (The manometer should show almost no pressure, because 

the main manual gas valve is closed.) 

5.  After the Trial for Ignition Period, the 60200FR will lockout and turn 

on the red LED. The ignitor will shut off and the gas valve will close. 

Turn off power and set controls to stop call for heat.

6.  If Lockout does not occur, replace the 60200FR control.

Summary of Contents for 301GAS

Page 1: ...el 60200FR microprocessor control Agencies UL Listed Installer servicer Except where specifically stated other wise this manual must be used only by a qualified service technician In the state of Mass...

Page 2: ...nually for start up and burner appliance service When servicing the burner Disconnect electrical supply to burner before attempting to service to avoid electrical shock or possible injury from moving...

Page 3: ...ge omitted for clarity with powder coat paint finish 15 Flame rod insulator assembly 16 Combustion head 17 Gas saddle connection gasket 18 Gas manifold 19 Ignition electrode insulator assembly 20 Stat...

Page 4: ...chimney that has one or more sides exposed to the outside Install a listed stainless steel liner to vent the flue products A defective vent system could result in severe personal injury death or subst...

Page 5: ...iance instruction manual when available to size combustion air openings Use the following guidelines when appliance instructions are not available All air from inside building building must be well ve...

Page 6: ...amic fiber or Fiberglass insulation Ceramic fiber materials such as chamber liners may contain carcinogenic particles chrystobalites after exposure to heat Airborne particles from fiberglass or cerami...

Page 7: ...ner does not comply with the specifications of Table 1 and other guidelines in this manual Combustion head air tube configurations 301GAS burners are supplied with either an B or C head and air tube c...

Page 8: ...g b Close the manual gas valve on the gas supply line c Disconnect the burner gas train union d Remove the gas pipe at the burner air tube e Remove the four nuts securing the burner hinged door flange...

Page 9: ...x a Match wire colors of the incoming wires to those pre wired to the terminal strip inside the gas train J box b See the label in the burner junction box or the wiring diagram on page 11 Gas valve ve...

Page 10: ...supply pressure 14 inches w c Minimum supply pressure 5 inches w c Do not expose the gas train to gas pressure in excess of 14 inches water column Higher pressure could damage the valve seat resultin...

Page 11: ...hite wires are from the 120 vac HOT side and that the power is no less than 102 vac nor more than 132 vac Checking burner flame signal The 60200FR uses flame rectification to detect the flame Because...

Page 12: ...oap suds mixture to all gas piping joints near burner and check for any leaks If any leaks appear repair before proceeding Figure 12 Air band adjustment and retest Set burner air band See Figure 12 Lo...

Page 13: ...e control will restart Releasing the button before the LED s turn off will cause the control to remain in latch up The 60200FR control will not reset from lockout or latch up if power is interrupted P...

Page 14: ...firing rate Preparation before checkout Burner appliance installed per appliance instruction manual Burner components verified against Table 1 page 7 Burner appliance installed per all applicable cod...

Page 15: ...pressure switch to a pressure less than actual manifold pressure The high gas pressure switch should shut the burner down Replace the switch if necessary Turn off power to the appliance burner remove...

Page 16: ...ng studs Perform the complete checkout procedures of pages 12 through 15 including system inspection and checks 6 Maintenance and service procedures Maintenance service procedures Cleaning blower whee...

Page 17: ...Model 301GAS burner Instruction manual Carlin part number MN301GAS Rev 11 24 14 17 Where appliance instructions differ from this manual follow the appliance instructions 7 Troubleshooting...

Page 18: ...mary voltage to ignitor If ignitor receives 120 VAC and doesn t generate spark replace ignitor Airflow Check air band setting against Table 1 page 7 Wrong orifice size Verify orifice size per Table 1...

Page 19: ...flange burner verify the insertion depth on the appliance and burner see page 7 If using the adjustable flange Figure 14 measure the appliance inser tion depth to the set the position of the flange on...

Page 20: ...augmenter NA 5 Air band four slot 47001S 6 Air shutter low input range B head tube Air shutter mid input range C head tube 99254 99278 7 Blower wheel 5 diameter x 4 deep 28563S 8 Motor Carlin PSC 1 6...

Page 21: ...al follow the appliance instructions 9 Replacement parts Burner continued 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 Set screws Burnerisshownwithweldedflange suppliedonlyonburners ordered for specif...

Page 22: ...box 99517 7 Primary gas valve Honeywell V48A 1 NPT Bleed restrictor fixed 99227 99228 8 Pipe nipple schedule 40 steel 1 NPT x 4 long Obtain locally 9 Pipe nipple schedule 40 steel 1 NPT x 2 long Obta...

Page 23: ...301GAS burner Instruction manual Carlin part number MN301GAS Rev 11 24 14 23 Where appliance instructions differ from this manual follow the appliance instructions 9 Replacement parts Gas train conti...

Page 24: ...Model 301GAS burner Instruction manual Carlin part number MN301GAS Rev 11 24 14 24 Where appliance instructions differ from this manual follow the appliance instructions...

Reviews: