18
ENG
“SmartCella 3PH” +0500119IE - rel. 1.2 - 10.03.2017
3. USER
INTERFACE
3.1 Display
Signals on the display
Icon Function
Normal
operation
Start-up
ON
OFF
Blink
COMPRESSOR
compressor on
compressor off compressor
call
FAN
fan on
fan off fan
call
DEFROST
defrost in progress
defrost not required
defrost call
AUX
AUX output active
AUX output not active
anti-sweat heater function active
ALARM
delayed external alarm (before expiry
of time ‘A7’)
no alarm present
alarms and malfunctions
CLOCK
at least one timed defrost has been
set
no timed defrost has been
set
ON if RTC fi tted
ON if RTC fi tted
LIGHT
auxiliary-light output active
auxiliary-light output not
active
anti-sweat heater function active
SERVICE
no malfunction
no malfunction
malfunction (e.g. EEPROM error or
faulty probes)
HACCP
function enabled (HA and/or HF)
function enabled (HA and/
or HF)
function not enabled, HACCP
alarm saved
CONTINUOUS CYCLE
function activated
function not activated
function request
Tab. 3.a
3.2 Keypad
Buttons on the keypad
Button
Normal operation
Start-up
Pressing the button alone
Combination of buttons
PRG/MUTE
if pressed for more than 3 seconds, accesses
the menu for setting the password to access
type “F” (Frequent) or “C” (Confi guration)
parameters
if there is an active alarm: mutes the audible alarm
(buzzer) and deactivates the alarm relay
PRG+ON-OFF/UP: if pressed together for more than 3 s
resets any alarms with manual reset
if pressed and held for more than
5 seconds at start-up, activates the
procedure for setting the default
parameters
ON-OFF/UP if pressed for more than 3 seconds, switches
off the controller / if pressed for more than 1 s
switches on the controller
when setting the parameters, increases the
value displayed or scrolls to the next parameter
ON-OFF/UP+AUX/DOWN: if pressed together for more than 3 seconds, activates/deactivates the
continuous cycle
ON-OFF/UP+ SET/DEF: if pressed together for more than 3 seconds, displays the temperature read
by defrost probe 1
ON-OFF/UP+ PRG/MUTE: if pressed together for more than 3 seconds, resets any alarms with
manual reset
AUX/DOWN if pressed for more than 1 second, activates/
deactivates the auxiliary output
when setting the parameters, decreases the
value displayed or scrolls to the previous
parameter
AUX/DOWN + ON-OFF/UP: if pressed together for more than 3 seconds, activates/deactivates the
continuous cycle
AUX/DOWN + SET/DEF: if pressed together for more than 1 second, displays a submenu used to
access the parameters relating to HACCP alarms (HA, HAn, HF, HFn, if available)
SET/DEF
if pressed for more than 1 second, displays
and/or sets the set point
if pressed and held for more than 5 seconds,
starts a manual defrost
SET/DEF+ AUX/DOWN: if pressed together for more than 1 second, displays a submenu used to
access the parameters relating to HACCP alarms (HA, HAn, HF, HFn, if available)
SET/DEF+ ON-OFF/UP: if pressed together for more than 3 seconds, displays the temperature read
by defrost probe 1
Tab. 3.b
3.3 Signal
LEDs
Icon
Colour
Function
Status
Notes
ON
OFF
Green
POWER
Auxiliary circuit powered
Auxiliary circuit not powered
LED on depending on the status (ON) of circuit
breaker QF2 and disconnect switch QS1
Yellow
COMPRESSOR
Power available at compressor
power terminals
No power at compressor power
terminals
LED on depending on the status (ON) of motor
protector QM1 and whether power is available
Yellow
EVAPORATOR
FAN
Power available at evaporator fan
power terminals
No power at evaporator fan
power terminals
LED on depending on the status (ON) of circuit
breaker QF1 and whether power is available
Yellow
DEFROST
Power available at defrost power
terminals
No power at defrost power
terminals
LED on depending on the status (ON) of circuit
breaker QF1 and whether power is available
Red
ALARM
Alarm activated
Normal operation
LED on depending on: activation of circuit
breaker QF1 and/or motor protector QM1
and/or alarm input (high pressure switch or
compressor Kriwan)
Tab. 3.c
Note:
the status of the LED (On/Off ) obviously depends on the
operating logic of the panel (e.g. if the temperature reaches the set point,
the compressor and the corresponding LED will be switched off by the
electronic controller, without generating alarms)
Summary of Contents for SmartCella 3PH
Page 2: ......
Page 4: ......
Page 6: ......
Page 11: ...11 ITA SmartCella 3PH 0500119IE rel 1 2 10 03 2017 2 1 2 Codici WP00B57B20 WP00B47B20 Fig 2 b...
Page 12: ...12 ITA SmartCella 3PH 0500119IE rel 1 2 10 03 2017 2 2 Circuito ausiliario Fig 2 c...
Page 13: ...13 ITA SmartCella 3PH 0500119IE rel 1 2 10 03 2017 Fig 2 d...
Page 24: ......
Page 26: ......
Page 32: ...12 ENG SmartCella 3PH 0500119IE rel 1 2 10 03 2017 2 2 Auxiliary circuit Fig 2 c...
Page 33: ...13 ENG SmartCella 3PH 0500119IE rel 1 2 10 03 2017 Fig 2 d...
Page 43: ......