Carel SmartCella 3PH Quick Manual Download Page 1

H i g h   E f f i c i e n c y   S o l u t i o n s

SmartCella 3PH

Guida rapida

Quick guide

Controllo elettronico per celle frigorifere trifase

Electrical controller for three-phase cold rooms

NO POWER 

& SIGNAL 

CABLES 

TOGETHER

READ CAREFULLY IN THE TEXT!

Summary of Contents for SmartCella 3PH

Page 1: ...c y S o l u t i o n s SmartCella 3PH Guida rapida Quick guide Controllo elettronico per celle frigorifere trifase Electrical controller for three phase cold rooms NO POWER SIGNAL CABLES TOGETHER READ...

Page 2: ......

Page 3: ...pulire il dispositivo Non utilizzare il prodotto in ambiti applicativi diversi da quanto speci cato nel manuale tecnico Tutti i suggerimenti sopra riportati sono validi altres per il controllo schede...

Page 4: ......

Page 5: ...tiche tecniche 9 1 8 Codici opzioni 9 1 9 Montaggio e collegamenti 9 2 SCHEMI ELETTRICI 10 2 1 Circuito di potenza 10 2 2 Circuito ausiliario 12 2 3 Morsettiera 14 2 4 Collegamenti per funzionamento c...

Page 6: ......

Page 7: ...Veri care le cause dell intervento delle protezioni prima di ripristinarle In caso di guasto sostituire i componenti con altri aventi stesse caratteristiche e portate di quelli da sostituire Test Col...

Page 8: ...1x380x168 Materiali coperchio in policarbonato fondo in tecnopolimero Display cifre 3 digit LED visualizzazione da 99 a 999 stati di funzionamento indicati con icone gra che su display stati dei caric...

Page 9: ...rsetti 11 e 12 della scheda elettronica 1 8 Codici opzioni Codice Descrizione IROPZDSP00 interfaccia display remoto IR00XGD000 display ripetitore remoto IROPZ485S0 interf RS485 scheda seriale con rico...

Page 10: ...10 ITA SmartCella 3PH 0500119IE rel 1 2 10 03 2017 2 SCHEMI ELETTRICI 2 1 Circuito di potenza 2 1 1 Codici WP00B44A10 WP00B34A10 WP00B24A10 WP00B14A10 Fig 2 a...

Page 11: ...11 ITA SmartCella 3PH 0500119IE rel 1 2 10 03 2017 2 1 2 Codici WP00B57B20 WP00B47B20 Fig 2 b...

Page 12: ...12 ITA SmartCella 3PH 0500119IE rel 1 2 10 03 2017 2 2 Circuito ausiliario Fig 2 c...

Page 13: ...13 ITA SmartCella 3PH 0500119IE rel 1 2 10 03 2017 Fig 2 d...

Page 14: ...esso alimentazione Ingresso L2 L3 N Tab 2 e Morsettiera Numero Descrizione Tipo XA1 101 Pressostato LP Ingresso 102 104 Valvola solenoide Uscita 105 106 Termico ventilatore Ingresso 107 108 Termostato...

Page 15: ...azione Ingresso L2 L3 N Tab 2 g Morsettiera Numero Descrizione Tipo XA1 101 Pressostato LP Ingresso 102 104 Valvola Uscita 105 106 Termico ventilatore Ingresso 107 108 Termostato di sicurezza Ingresso...

Page 16: ...101 102 Fig 2 h Note dal momento che il pressostato collegato ai morsetti 101 102 non abilitare il pump down su Smartcella 3PH veri care che c7 0 H1 5 2 4 2 Connessioni per pump down in pressione con...

Page 17: ...ig 2 l Note non abilitare il pump down su Smartcella 3PH veri care che c7 0 H1 5 2 4 4 Connessioni per pump down a tempo Nel caso in cui sia necessario avere un avviamento e spegnimento della valvola...

Page 18: ...tano gli eventuali allarmi a ripristino manuale AUX DOWN se premuto per pi di 1 s attiva disattiva l uscita ausiliaria durante la modi ca dei parametri decrementa il valore visualizzato o fa passare a...

Page 19: ...0 20 0 0 St Set point C F F r1 r2 0 0 rd Di erenziale C F F 0 1 20 2 0 rn Zona neutra C F C 0 0 60 4 0 rr Di erenziale reverse C F C 0 1 20 2 0 r1 Set point minimo C F C 50 r2 50 r2 Set point massimo...

Page 20: ...unning time C F C 20 20 1 0 d12 Sbrinamenti avanzati C 0 3 0 dn Durata nominale sbrinamento C 1 100 65 dH Fattore proporzionale di variazione di dI C 0 100 50 A0 Di erenziale allarmi e ventilatori C F...

Page 21: ...ente eccitato 1 allarme normalmente diseccitato 2 ausiliaria 3 luce 4 sbrinamento evaporatore ausiliario 5 valvola pump down 6 ventilatore condensatore 7 compressore ritardato 8 ausiliaria con disatti...

Page 22: ...ON autom man autostart in pump down cht nessuna OFF OFF autom man preallarme alta temperatura condensatore CHT lampeggiante ON ON manuale allarme alta temperatura condensatore dor lampeggiante ON ON a...

Page 23: ...se corrosive chemicals solvents or aggressive detergents to clean the device Do not use the product for applications other than those speci ed in the technical manual All of the above suggestions like...

Page 24: ......

Page 25: ...stics 8 1 7 Technical speci cations 9 1 8 Option part numbers 9 1 9 Assembly and connections 9 2 WIRING DIAGRAMS 10 2 1 Power circuit 10 2 2 Auxiliary circuit 12 2 3 Terminal block 14 2 4 Connections...

Page 26: ......

Page 27: ...tting the protection devices In the event of faults replace the components with others that have the same features and ratings as those being replaced Testing Panel functional testing check output vol...

Page 28: ...characteristics Casing plastic dimensions 491x380x168 Materials polycarbonate cover technopolymer shell Display digits 3 digit LED display from 99 to 999 operating status indicated by graphic icons o...

Page 29: ...irectly to terminals 11 and 12 on the electronic board 1 8 Option part numbers P N Description IROPZDSP00 remote display interface IR00XGD000 remote repeater display IROPZ485S0 RS485 serial card with...

Page 30: ...10 ENG SmartCella 3PH 0500119IE rel 1 2 10 03 2017 2 WIRING DIAGRAMS 2 1 Power circuit 2 1 1 Part numbers WP00B44A10 WP00B34A10 WP00B24A10 WP00B14A10 Fig 2 a...

Page 31: ...11 ENG SmartCella 3PH 0500119IE rel 1 2 10 03 2017 2 1 2 Part numbers WP00B57B20 WP00B47B20 Fig 2 b...

Page 32: ...12 ENG SmartCella 3PH 0500119IE rel 1 2 10 03 2017 2 2 Auxiliary circuit Fig 2 c...

Page 33: ...13 ENG SmartCella 3PH 0500119IE rel 1 2 10 03 2017 Fig 2 d...

Page 34: ...vaporator fan Output 2 3 Condenser fan Output 8 4 Defrost heaters Output 5 6 7 9 Crankcase heater Output 10 11 Compressor Output 12 13 L1 Power supply input Input L2 L3 N Tab 2 d Terminal block Number...

Page 35: ...ut 2 3 4 Condenser fan Output 10 5 Defrost heaters Output 6 7 8 11 Crankcase heater Output 12 13 Compressor Output 14 15 L1 Power supply input Input L2 L3 N Tab 2 f Terminal block Number Description T...

Page 36: ...low pressure terminals 101 102 Fig 2 h Note as the pressure switch is connected to terminals 101 102 do not enable pump down on Smartcella 3PH check that c7 0 H1 5 2 4 2 Connections for pump down by p...

Page 37: ...M2 are o simultaneously Fig 2 l Note do not enable pump down on Smartcella 3PH check that c7 0 H1 5 2 4 4 Connections for pump down by time If solenoid valve needs to be activated and deactivated by t...

Page 38: ...ed together for more than 3 seconds resets any alarms with manual reset AUX DOWN if pressed for more than 1 second activates deactivates the auxiliary output when setting the parameters decreases the...

Page 39: ...20 0 0 c5 Probe 5 calibration C F C 20 20 0 0 St Set point C F F r1 r2 0 0 rd Di erential C F F 0 1 20 2 0 rn Neutral zone C F C 0 0 60 4 0 rr Reverse di erential C F C 0 1 20 2 0 r1 Minimum set point...

Page 40: ...ture threshold C F C 20 20 1 0 d12 Advanced defrosts C 0 3 0 dn Nominal defrost duration C 1 100 65 dH Proportional factor for variation of dI C 0 100 50 A0 Alarm and fan di erential C F C 0 1 20 2 0...

Page 41: ...H0 Serial address C 0 207 1 H1 AUX1 output con guration 0 normally energised alarm 1 normally de energised alarm 2 auxiliary 3 light 4 auxiliary evaporator defrost 5 pump down valve 6 condenser fan 7...

Page 42: ...e alarm AtS ashing ON ON auto man autostart in pump down cht none OFF OFF auto man high condenser temperature pre alarm CHT ashing ON ON manual high condenser temperature alarm dor ashing ON ON automa...

Page 43: ......

Page 44: ...EL INDUSTRIES S p A Via dell Industria 11 35020 Brugine Padova Italy Tel 39 049 9716611 Fax 39 049 9716600 e mail carel carel com www carel com Agenzia Agency SmartCella 3PH 0500119IE rel 1 2 10 03 20...