9. INFORMATION 

SCREENS

Screen Aa67 has been added to the information screens. This shows the status and activation percentage of 
the parallel compression function, the current fl ash valve set point and the receiver pressure:

This screen is available for all parallel compression confi guration modes: integrated, external via pLAN and 
external with connection via digital I/O. For the latter, the percentage displayed will be 0% or 100%, relating 
to the feedback signal, indicating activation or deactivation of parallel compression.

In the event of confi guration with integrated modulating compressor control, screen Aa77 will also show the 
parallel compression discharge temperature:

Summary of Contents for pRack pR300T

Page 1: ...I n t e g r a t e d C o n t r o l S o l u t i o n s E n e r g y S a v i n g s Manuale d uso User manual Parallel compression for transcritical systems Function available for pRack pR300T controller...

Page 2: ......

Page 3: ...compressore modulante 9 Due o pi compressori 9 6 FUNZIONAMENTO CON SCHEDA ESTERNA E I O DIGITALI 10 Con gurazione della scheda principale 10 Con gurazione della scheda per la compressione parallela 1...

Page 4: ......

Page 5: ...tura a lavorare maggiormente e con un elevata di erenza di pressione tra aspirazione e scarico L utilizzo di un compressore o di una batteria di compressori posti tra il ricevitore e lo scarico dei co...

Page 6: ...tire la compressione parallela 1 tramite scheda esterna e ingressi uscite digitali per il controllo Fig 2 a 2 via rete pLAN con l utilizzo di una scheda dedicata con indirizzo 9 Fig 2 b 3 come funzion...

Page 7: ...care il valore delle sopracitate soglie La compressione parallela viene disattivata con il conseguente ripristino del setpoint nominale per la valvola RPRV se si veri ca almeno una delle condizioni s...

Page 8: ...OFF REGOLAZIONE ON REGOLAZIONE ON REGOLAZIONE ON CHIUSA 1 Richiesta per la compressione parallela 2 Feedback dalla compressione parallela 3 Richiesta di incremento del set point per la valvola flash...

Page 9: ...re modulante si raccomanda una regolazione di tipo proporzionale con integrazione di errore P I Il setpoint pu essere lo stesso utilizzato nella regolazione della pressione del ricevitore mediante val...

Page 10: ...controllore pRack Compact pR100 pR100T pR300 pR300T Tuttavia si raccomanda l utilizzo di un controllore per centrali transcritiche quindi pR100T o pR300T Configurazione della scheda principale Quando...

Page 11: ...si suggerisce di utilizzare la funzione di cambio setpoint da ingresso digitale Il vantaggio rispetto all utilizzo della funzione ON OFF da ingresso digitale che utilizzando quell ultima non c alcuna...

Page 12: ...ione Per quanto concerne l uscita digitale nella scheda per la compressione parallela connessa all ingresso sopracitato si suggerisce di usare una funzione generica che si attivi quando almeno un comp...

Page 13: ...int e del di erenziale per l attivazione 1 per entrambi i parametri 4 associazione di un rel di uscita per la funzione generica usata come feedback Seguendo l esempio sopra descritto si ottiene la con...

Page 14: ...le Questo tipo d con gurazione richiede l utilizzo di una scheda pR300T per la compressione parallela con la stessa versione software utilizzata nella scheda principale L indirizzo di rete della sched...

Page 15: ...ne simultanea dei tasti UP ENTER DOWN La con gurazione di rete risulter come illustrato nella gura seguente Fig 7 c VANTAGGI rispetto al controllo della compressione parallela tramite un ingresso e un...

Page 16: ...da pRack principale pLAN1 per controllare anche la compressione parallela attraverso l utilizzo di un dispositivo modulante La maschera Cca04 permette di speci care il setpoint e i parametri di regola...

Page 17: ...la gestione integrata del compressore viene reso disponibile un allarme da ingresso digitale con gurabile tramite le machere Cca11 e Cca12 E possibile inoltre con gurare un allarme di alta temperatur...

Page 18: ...ore Questa maschera disponibile per tutte le modalit di con gurazione della compressione parallela interna esterna via pLAN ed esterna con collegamento tramite I O digitali Per quest ultima la percent...

Page 19: ...NTROL 9 One modulating compressor only 9 Two or more compressors 9 6 EXTERNAL CONTROL BOARD AND DIGITAL I O 10 Main board con guration 10 Parallel compression control board con guration 11 7 CONTROL B...

Page 20: ......

Page 21: ...ture compressors do more work and operate at a high suction discharge pressure di erence The use of a compressor or group of compressors installed between the receiver and medium temperature compresso...

Page 22: ...ree modes for managing parallel compression 1 control by external board and digital inputs outputs Fig 2 a 2 via pLAN network using a dedicated board with address 9 Fig 2 b 3 as an integrated function...

Page 23: ...02 is used to set the thresholds described above Parallel compression is deactivated and the standard RPRV valve set point restored when at least one of the following conditions occurs the pRack is sw...

Page 24: ...rg SET POINT RPRV 38 barg SET POINT RPRV 38 barg OFF CONTROL ON CONTROL ON CONTROL ON CLOSE 1 Parallel Compression Control 2 Parallel Compression Feedback 3 Control set point increase for flash valve...

Page 25: ...If there is only one modulating compressor proportional plus integral control P I is recommended The set point can be the same used for receiver pressure control using the ash valve One possible con...

Page 26: ...y this solution can be used with any pRack controller Compact pR100 pR100T pR300 pR300T Nonetheless it is recommended to use a controller for transcritical systems i e pR100T or pR300T Main board conf...

Page 27: ...of parallel compression using the set point variation from digital input function The advantage of this compared to the ON OFF from digital input function is that the latter does not feature an alarm...

Page 28: ...tion function As concerns the digital output on the parallel compression control board connected to the input described above it is recommended to use a generic function that is activated when at leas...

Page 29: ...cify the set activation point and di erential 1 for both parameters 4 associate an output relay for the generic function used as feedback The example described above will give the con guration illustr...

Page 30: ...k board This type of con guration requires the use of a pR300T board for managing parallel compression with the same software version as used on the main board The network address of the parallel comp...

Page 31: ...ng the UP ENTER DOWN buttons together The network con guration will be as illustrated in the following gure Fig 7 c ADVANTAGES compared to parallel compression control using a digital input and output...

Page 32: ...This mode allows the main pRack board pLAN1 to be used to also control parallel compression via a modulating device Screen Cca04 speci es the parallel compression set point and control parameters PID...

Page 33: ...05 Cca06 and Cca07 Given that compressor management is integrated an alarm from programmable digital input is made available on screens Cca11 and Cca12 In addition a dedicated high temperature alarm c...

Page 34: ...e This screen is available for all parallel compression con guration modes integrated external via pLAN and external with connection via digital I O For the latter the percentage displayed will be 0 o...

Page 35: ......

Page 36: ...CAREL INDUSTRIES HQs Via dell Industria 11 35020 Brugine Padova Italy Tel 39 049 9716611 Fax 39 049 9716600 e mail carel carel com www carel com Agenzia Agency 030220585 1 1 10 12 2015...

Reviews: