“optiMist” +0300065EN- rel. 1.1 - 29/01/2013
8.11 User menu
From the main screen press:
•
PROG to access the main menu;
•
ENTER to select and access the selected menu;
•
UP/DOWN to move between the submenus;
•
ENTER to enter the submenus
•
ENTER to select the parameter and move between the parameters;
•
UP/DOWN to modify the parameter;
•
ENTER to confi rm selected parameter and go to the next parameter;
•
ESC to return to the previous menu.
To navigate inside the screens:
•
UP or DOWN to modify the value (within the options/range),
•
ENTER to confi rm and move the cursor to the next value
•
ESC to return to the installer menu.
User menu screens:
1. User
1. Alarm threshold
2. Clock
3. Enable scheduler
4. Set scheduler
5. Weekly scheduler
6. Scheduled set point
Submenu:
1.Alarm threshold
If the zone dedicated to humidifi cation is confi gured, the following
screen appears:
Display
Description
Range
Def.
UoM
Main probe threshold
Alarm high
High humidity alarm threshold 0…100%rH
100 %rH %rH
Alarm low
Low humidity alarm threshold 0…100%rH
0 %rH
%rH
Limit probe thresh.
Alarm high
High humidity/temperature
limit alarm threshold
0…150°C/°F
o 0…100%rH
100 %rH °C o°F
o %rH
Alarm delay
Alarm signalling delay
0…99
1
min
Tab. 8.i
Where there is a zone dedicated to evaporative cooling, the following
screen will also appear:
Display
Description
Range Def.
UoM
Main probe threshold
Alarm high
High temper. alarm threshold 40 °C
100 %rH %rH
Alarm low
Low temper. alarm threshold 20 °C
0 %rH
%rH
Limit probe thresh.
Alarm high
High humidity/temperature
limit alarm threshold
40 °C
100 %rH °C o°F
o %rH
Alarm delay
Alarm signalling delay
0…99
1
min
Tab. 8.j
Submenu:
2.Clock
Display
Description
Range
Hour
Setting the time on the internal clock
Day
Setting the day on the internal clock
Month
Setting the month on the internal clock
Year
Setting the year on the internal clock
Format
Setting data format
dd/mm/yy - mm/dd/yy
Week day
Day of the week corresponding to the
date
Monday to Sunday
Tab. 8.k
Submenu:
3. Enable scheduler
Display
Description
Range
Def. UoM
Enable scheduler
Scheduler ON/
OFF
Enable scheduler
NO/YES NO
Delay schedu-
ler:
Temporarily shut down the optiMist
which will restart after ____ minutes
0…999 0
min
Tab. 8.l
Submenu:
4. Set scheduler
Note:
the screen is visible if “scheduler ON/OFF” has been enabled (see
enable scheduler screen).
Setting the intervals for the operation of the humidifi er over one day
(24h):
Display
Description
Ora ON
Ora OFF
P1-1
First P1 interval
9:00
13:00
P1-2
Second P1 interval
14:00
21:00
P2
First P2 interval
8:00
18:00
P3
Time slot always ON
ON always
P4
Time slot always ON
OFF always
Tab. 8.m
Parameters P1...P4 can be used to set how many times atomised water
production is enabled or disabled over a 24 hour period.
P
1
P
1
-
1
P
1
-2
P2
P
2
P
3
P
4
0
OFF
ON
ON
OFF
OFF
ON
ON
OFF
OFF
OFF
24
h
0
24
h
0
24
h
0
24
h
Fig. 8.c
P1
2 daily time slots ON
P2
Single time slot ON
P3
always ON
P4
always OFF
Submenu:
5. Weekly scheduler
Note:
the screen is visible if “scheduler ON/OFF” has been enabled (see
enable scheduler screen).
Setting of the weekly operation of the humidifi er, using parameters P1...
P4 (confi gured in the previous screen)
Display
Range
Monday
P1...P4
Tuesday
P1...P4
Wednesday
P1...P4
Thursday
P1...P4
Friday
P1...P4
Saturday
P1...P4
Sunday
P1...P4