6.8 Hot gas bypass
The hot gas by-pass in temperature mode function allows to increase the temperature of the output water from the evaporator. The output enabled is
the controller analogue output Y1 (water-water chiller) or Y2 (air-water chiller) of the I/O expansion board.
Par.
Description
Def
Min
Max
U.M.
H25
Hot gas by-pass
0/1 = disabled/enabled
0
0
1
-
H26
Hot gas by-pass in stand-by
0/1 = disabled/enabled
0
0
1
-
6.9 Pump down
This function allows the unit to be stopped while avoiding the possible formation of liquid refrigerant inside the evaporator. When the only active
compressor is called to stop, the expansion valve is closed so as to depressurise the circuit. Valid only when the driver is installed, as the driver
pressure probe is used
Par.
Description
Def
Min Max
U.M.
H13
Enable pump down
0
0
1
-
H14
Pump down minimum pressure
2
0
50
bar
H15
Pump down maximum time
30
0
180
s
6.10 Heaters management
r43 defines the relationship between absolute set-point, intended as electric heaters activation threshold and relative set-point, i.e. electric heaters
activation threshold referring to an operational set-point. For example, if r43 = 7, the anti-freeze/support heater will activate below the value of r01-
A04, instead of A04.
Par.
Description
Def
Min
Max
U.M.
r43
Heaters set-point:
0=A04, A08, A11, P16, P19 absolute
1=A04, P16, P19 absolute, A08, A11 relative
2=A08, A11, P16, P19 absolute, A04 relative
3=P16, P19 absolute, A04, A08, A11 relative
4=A04, A08, A11 absolute, P16, P19 relative
5=A04 absolute, A08, A11, P16, P19 relative
6=A08, A11 absolute, A04, P16, P19 relative
7=A04, A08, A11, P16, P19 relative
7
0
7
-
Regarding the activation set-points of the heaters, when the temperature measured by the probe B1/B2 (see A06) drops below the value of the
parameter A08/A11 the heater or heaters activates, if the respective outputs are set with the parameter H11.
A08
B1or B2
ON
A09
OFF
A11
A09
Key
B1/B2 Support heaters probe
Par.
Description
Def
Min
Max
U.M.
A06
Auxiliary heater probe
0=Control probe (B1)
1=Anti-freeze probe (B2)
0
0
1
-
A08
Heater 1 set point (see r43)
5
A01
80
°C/°F
A08
Heater 1 relative set point (see r43)
2
0
20
°C/°F
A09
Heaters differential
2
0.3
50
°C/°F
A11
Heater 2 set point (see r43)
7
A01
80
°C/°F
A11
Heater 2 relative set point (see r43)
7
0
20
°C/°F