2
ENGINEER USE ONLY
ICON
CODE
PARAMETER
DESCRIPTION
UOM
FRIDGE
FREEZER
DEFAULT
/A2
Configuration
Sets to FRIDGE/ FREEZER
Mode
0
2
St
Temperature set
point
(see 1
st
instruction)
Required temperature set
point in cabinet
°C
0.0
r1
Minimum set point
Minimum set point (St)
allowed
°C
r2
Maximum set
point
Maximum set point (St)
allowed
°C
200
200
60
60
-50
200
200
60
AUX
6
6
H2
Disable key pad
OPERATING INSTRUCTIONS CAREL IR33 (G60875, G60890)
AS A THERMOMETER ONLY
G60875 (230v)
G60890 (12/24v)
WIRING DIAGRAMS 230v and 12/24v
FAULT ALARMS
E0
Sensor S1 (cabinet temperature) failure
E1
Sensor S2 (defrost) failure
LO
Low temperature alarm
HI
High temperature alarm
dor
Excess time of open door
Etc
Real time clock failure
EE
Error in E.prom. Unit parameters
EF
Error in E-prom. Functioning parameters
IR33C0HH20
240v
115v
SUPPLY
PROBE
Terminal
Missing
12...24V
12...24V~300mA~max, 12...30 Vdc 300mAdc max
SUPPLY
PROBE
IR33Y0LR00
Maximum current on terminal 3: 12A
EN60730-1 12 (2) A
UL 873
12A 5FLA
30LRA
250V~
R1
THE ABOVE PROCEEDURE MUST BE CARRIED OUT IN THE EXACT ORDER OUTLINED