15
ENG
ir33+ wide Fullmotion - +040000055 - rel. 1.0 - 09.06.2014
Cod.
Parameter
Status
c1
Minimum time between successive starts of the second compressor
NOTE: only active for AUX if H1 =12
Standard
c2
Minimum second compressor OFF time
NOTE: only active for AUX if H1 =12
Standard
c3
Minimum second compressor ON time
NOTE: only active for AUX if H1 =12
Standard
c11
Second compressor start delay if H1 = 7 no temp. control of AUX compressor
Standard
Tab. 3.j
3.12 Pump down
The pump down function can be activated when the parameter
H1 = 5
and
c7 ≥ 7
.
The AUX relay is then dedicated to the pump down valve.
Digital input DI1 has to be configured as a low pressure switch
A4 = 8
or pump down will be performed by
time if
c10 = 1
.
To start with pump down, control of the Fullmotion compressor needs to stop, then pump down starts. An
immediate pump down can be performed by setting
cct = 0
.
If
c10 = 1
and no pressure switch is configured
(A4 = 8)
the pump down lasts for the time
c7
.
The compressor start can be delayed by the time
c8
.
Cod. Parameter
UOM Dis.
Type Def. Max
Min
c7
Maximum pump down time (PD)
0 = Pump down disabled
Sec
C
I
0
900
0
c8
Compressor start delay after opening PD valve
Sec
C
I
5
60
0
c9
Autostart in pump down
0 = Disabled
1 = Pump down whenever closing pump down valve &
following low pressure switch activation with no cooling
demand
-
C
1
1
0
c10 Pump down by time or pressure
0 = pressure
1 = time
-
C
D
0
1
0
A4
Digital input 1 configuration (DI1)
8 = low pressure switch
min
C
0
1
0
H1
Configure function of output AUX1
5 = pump down valve
7 = delayed compressor (see c11)
11 = reverse with neutral zone
12 = second compressor
13 = no function
14 = drain heater management
-
C
I
14
14
0
Tab. 3.k
3.13 OFF from keypad
Pressing the ON/OFF button for more than 3 seconds switches the controller ON/OFF.
If speed control is running, the Fullmotion compressor is forced to run at the minimum speed set by
cmf
for
a fixed time of 30 sec.
If the controller is configured for pump down, the controller activates pump down management.