DPDQ 502000

  

including mounting flange

DPDQ 502000

APPLICATION:
Patented quality product  (patent no. DE 10 2014 010 719.1)

The maintenance-free, microprocessor-controlled duct sensor is used to monitor the CO

 con-

centration as well as air quality (VOC). All measurands are converted to standard signals (0 -10 V 
or 4...20 mA). The duct sensor measures CO

2

 in the range of 0...2000 ppm or 0...5000 ppm, VOC 

at one of three selectable sensitivity levels LOW / MEDIUM (default) / HIGH. The CO

2

 content of 

the air is measured using an optical NDIR sensor (non-dispersive infra-red technology). The detec-
tion range of the sensors is calibrated for standard applications such as monitoring residential 
rooms and conference rooms. Room ventilation on an as-needed basis,  improved well-being and 
customer benefit, increased comfort as well as reduced operating costs through energy conservation are 
just some of the benefits of employing the CO

2

 sensor. The  explanations above demonstrate that there are 

applications for CO

2

 measurements, for VOC measure ments, but from our perspective, above all, for a 

combination of both measurands. The crucial factor in this respect is that both of these measurands are 
not convertible into each other and derivations to or from one another cannot be made. An NDIR CO

measuring instrument  measures selectively and cannot detect any VOC; a VOC mixed gas sensor cannot 
recognize CO

2

 molecules.  

TECHNICAL DATA:

Power supply: 

24 V AC ⁄ DC (± 10 %)

Power  consumption:  

<  4.8  W  ⁄  24 V  DC   typical;    <  6.8 VA  ⁄  24 V  AC  typical;     

peak  current  200  mA

Outputs: 

0 -10 V

 or 

4...20 mA

  (selectable via DIP switches,  

selected variant applies for all outputs), working resistance  < 800  Ω

AIR QUALITY  (VOC)

Sensor, VOC : 

VOC sensor (metal oxide) 

with automatic calibration

 

(VOC = volatile organic compounds)

Measuring range, VOC : 

0...100 % air quality; referred to calibrating gas;  

multi-range switching

  

(selectable via DIP switches) – VOC sensitivity low, medium, high

Output,  VOC : 

0 -10 V

    (0 V  =  clean  air,  10 V  =  polluted  air)  or 

4...20 mA

 (selectable via DIP switches,  

switchpoint can be adjusted from 0...100 % of the output signal)

Measuring accuracy, VOC : 

± 20 % of final value  (referred to calibrating gas) 

Service life: 

> 60 months  (under normal load conditions)

CARBON DIOXIDE (CO

2

)

Sensor, CO

2

:   

optical NDIR sensor (non-dispersive infra-red technology) 

including atmospheric pressure compensation (up to 1100  mbar) 

with automatic and manual calibration

Measuring range, CO

2

:   

multi-range switching

 (selectable via DIP switches) – 0...2000  ppm; 0...5000  ppm

Output, CO

2

:  

0 -10 V

 or 

4...20 mA

  (selectable via DIP switches)

Measuring accuracy, CO

2

:  

± 30 ppm  ± 3 %  of  measured  value

Temperature dependence, CO

2

:  ± 5 ppm   ⁄  °C  or  ± 0.5 %  of  measured  value   ⁄  °C    (whichever  is  higher)

Pressure  dependence:  

± 0.13 %   ⁄  mm  Hg

Long-term stability:  

< 2 % in 15 years

Gas exchange:  

by diffusion

Relay output:  

with potential-free changeover contact 24 V  (assignment selectable via DIP switches)

Ambient  temperature: 

–10...+60 °C

Operating range, humidity:  

0...95 % r. H.  (without dew formation)

Response time: 

< 2 minutes

Electrical connection: 

0.14 - 1.5 mm

2

, via screw terminals

Enclosure:  

plastic, polyamide, 30 % glass-globe reinforced, with quick-locking screws  

(slotted ⁄ Phillips head combination), colour traffic white (similar to RAL 9016)

Enclosure  dimensions: 

126  x  90  x  50 mm

Cable gland:  

M 16 x 1.5; including strain relief, exchangeable

Protective tube: 

PLEUROFORM

TM

, material polyamide (PA6), with torsion protection,  

Ø  20 mm, v

max

 = 30  m/s (air), NL = 202.5 mm

Process connection: 

via flange made of plastic  (included in scope of delivery)

Protection class: 

III  (according to EN 60 730)

Protection type: 

IP 65  (according to EN 60 529)  enclosure only!  (PLEUROFORM IP 30)

Standards: 

CE conformity, electromagnetic compatibility according to EN 61 326,  

EMC Directive 2014 ⁄ 30 ⁄ EU 

Summary of Contents for DPWQ502000

Page 1: ...rating instructions mounting installation DPWQ 502000 Room air quality VOC and CO2 sensor with self calibrating with multi range switching active and switching output DPDQ 502000 including mounting fl...

Page 2: ...tchpoint can be adjusted from 0 100 of the output signal Measuring accuracy VOC 20 of final value referred to calibrating gas Service life 60 months under normal load conditions CARBON DIOXIDE CO2 Sen...

Page 3: ...or Reset button NC COM NO relay switch point Type WG02 Measuring Range CO2 Measuring Range VOC Output VOC CO2 Features DPWQ 502000 0 2000 0 5000 ppm 0 100 0 10 V 4 20 mA Changeover contact Note This u...

Page 4: ...latile organic compounds Measuring range VOC 0 100 air quality referred to calibrating gas multi range switching selectable via DIP switches VOC sensitivity low medium high Output VOC 0 10V 0 V clean...

Page 5: ...ype WG02 Measuring Range CO2 Measuring Range VOC Output VOC CO2 Features DPDQ 502000 0 2000 0 5000 ppm 0 100 0 10 V 4 20 mA Changeover contact Note This unit must not be used as safety relevant device...

Page 6: ...of approx 4 weeks the minimum output value for air quality is saved After this period the output signal is standardised to the zero point 1 0 V The maximum amount of correction per interval is limite...

Page 7: ...se to heat sources e g radiators or be exposed to their heat flow Direct sun irradiation or heat irradiation by similar sources powerful lamps halogen spotlights must absolutely be avoided Operating t...

Page 8: ...ller of the final equipment accepts all liability and risk relating to the configuration of the product in order to reach the expected results in relation to the specific installation and or equipment...

Reviews: