12
UK
SETTING OPERATION
Load ON/OFF Setting
When the controller is powered on, press the button to control the load output.
Battery Type Setting
Step 1: Enter setting mode by pressing button for 5s until the battery status
LEDs are flashing.
Step 2: Select the desired mode by pressing button.
Step 3: The mode will be saved automatically without any operation for 5S and
LED will stop flashing.
Batterie Typ
LED 1
LED 2
LED 3
Sealed (Default)
ON
-
-
GEL
ON
ON
-
Flooded
ON
ON
ON
PROTECTION
Battery Over Voltage Protection
When the battery voltage reaches to the set point of Over Voltage Disconnect
Voltage (OVD), the controller will stop charging the battery to protect the battery
from being over charged to break down.
Battery Over Discharge Protection
When the battery voltage reaches to the set point of Low Voltage Disconnect
Voltage (LVD), the controller will stop discharging the battery to protect the
battery from being over discharged.
Load Overload Protection
When the load is overloading (The overload current is ≥1.02 times, 1.05 times,
1.25 times, 1.35 times, 1.5 times the rated load current), the controller will
automatically cut off the output after 50s, 30s, 10s, 2s and 0.5s. User has to
reduce load appliance, then press the button or repower the controller.
Load Short Circuit Protection
Load will be switched off when load short circuit happens. User has to clear
short circuit, then press the button or repower the controller.
High Voltage Transients Protection
The controller is protected against small high voltage transients. In lightning
prone areas, additional external suppression is recommended.