13
Modbus Communication Wiring
Each RTULink will need to have a path of communication to the communication module (PN: COMM01 located in the
hood panel) via a CAT5 cable. The communication module is typically located in a kitchen ventilation hood control panel,
however it is not limited to that specific location. In most cases, wiring a daisy chain configuration will require the least
amount of wire. See APPENDIX A for typical network layouts in order to determine the best configuration for the
application. Use the J1 and J2 RJ45 ports to connect the RTULinks together using the CAT5 cable. If an RTULink is the
last in a line, it will only have one CAT5 cable connected to it and will require an end of line resistor (PN:
EOL120A) in its
unused port (J1 or J2).
shows a wiring detail for the Modbus communication network.
All CAT5 cables should be run without RJ45 connectors, and a crimp tool should be used to add connectors once wire
routing is complete. Each RJ45 connector wire should be wired in a T-568-B straight-through configuration. See
if you are unfamiliar with how to make a straight-through CAT5 cable using RJ45 connectors and a crimp
tool. Once complete, a CAT5 tester should be used to test each length of wire.
Figure 11. Modbus Network
– RTULink Wiring
Summary of Contents for RTULink
Page 2: ...2...
Page 30: ...30 Main Board HMI Menu Tree...
Page 31: ...31...
Page 32: ...32...
Page 33: ...33...
Page 34: ...34...
Page 41: ...41...
Page 42: ...42...
Page 43: ...43...
Page 44: ...44...
Page 52: ...52 APPENDIX C Fixed Dry Bulb Economizer Figure 34 Fixed Dry Bulb Economizer Operation...
Page 53: ...53 Differential Dry Bulb Economizer Figure 35 Differential Dry Bulb Economizer Operation...
Page 54: ...54 Fixed Enthalpy Economizer Figure 36 Fixed Enthalpy Economizer Operation...
Page 55: ...55 Differential Enthalpy Economizer Figure 37 Differential Enthalpy Economizer Operation...