11
Space Thermistor
– Wall Mount (optional)
If a space temperature sensor/thermistor is called for in the specifications, follow the instructions in this section.
Note: This is not to be confused with the traditional space stat that is used for commercial kitchen ventilation
electrical packages.
A space thermistor will need to be
installed in the zone being supplied
by the RTU. Install a junction box in
an area that will provide accurate
temperature readings. Avoid areas
near windows that are exposed to
sunlight, areas near diffusers, areas
near appliances, areas more than 6
ft. above the floor, etc. Route the
thermistor wire to the RTULink and
connect it to the + and C terminals
(thermistor input is not polarity
sensitive)
on the “RTU” side of the
RTULink labeled “SPACE TEMP
10kΩ”. Use the mounting screws
provided with the sensor to secure
the sensor to the junction box.
for a stainless steel space thermistor
(PN: A/CP-SP).
installation detail for a space
thermistor with a plastic housing (PN:
A/CP-R2).
shows the space sensor terminals and wiring detail.
Figure 7. Thermostat - RTULink Installation Detail
Figure 8. Space Thermistor Detail (Stainless Steel Housing Wall Mount)
Summary of Contents for RTULink
Page 2: ...2...
Page 30: ...30 Main Board HMI Menu Tree...
Page 31: ...31...
Page 32: ...32...
Page 33: ...33...
Page 34: ...34...
Page 41: ...41...
Page 42: ...42...
Page 43: ...43...
Page 44: ...44...
Page 52: ...52 APPENDIX C Fixed Dry Bulb Economizer Figure 34 Fixed Dry Bulb Economizer Operation...
Page 53: ...53 Differential Dry Bulb Economizer Figure 35 Differential Dry Bulb Economizer Operation...
Page 54: ...54 Fixed Enthalpy Economizer Figure 36 Fixed Enthalpy Economizer Operation...
Page 55: ...55 Differential Enthalpy Economizer Figure 37 Differential Enthalpy Economizer Operation...