Caple WI6225 Technical Information Download Page 16

 

 

10

 

 

  How to replace the sensor 

 

The process of sensor removed: remove the shelves

remove the airduct board

disconnect the connectors

remove the sensor cover

remove the sensor 

 

The sensor are fix on the airduct board(two zone are same) 

A. Remove the shelves. 

(

3) (Fig.1)   

B. Remove the air duct board. See

 (

4) (Fig.2) 

C.  Push  and  then  pull  out  the  two  plastic  nails(1,2),the  sensor  cover

(3)

  come  loose,  disconnect  the 

connector

(5)

 of the sensor, and replace it

(4). ( Fig.8)

 

 

 

 

  Refrigerant valve fault 

 

The  process  of  valve  removed:  remove  the  cover  of  the  valve

disconnect  the  connectors

disjoin  the 

soldered joints

remove valve 

 

1 >

If the temperature of either zone of left and right is normal, and another zone is not cooling, or over 

low temperature, (lower than the temperature preset 3

), or one zone is not cooling the other zone 

is over cold, please check the refrigerant valve. 

 

2  >

Turn  off  the  power,  exchange  the  two  poles  of  the  refrigerant  valve,  and  turn  on  the  power  again, 

please pay attention to the sound snip-snap, or the refrigerant valve out off power or ruins. Replace 

the same module

s refrigerant valve when confirming the PCB board is normal. 

 

3 >

  How to replace the refrigerant valve: 

A.

 

Use  welding  facility  to  heat  the  3  welding  point  H,  K  ,  J,  and  then  take  off  the  refrigerant 

valve. 

(Fig. 9)

 

B.  Use  the  cross  screwdriver  to  wrest  the  refrigerant  welding  screw  1  (totally  2pcs,  another  isn

show in the picture.

(Fig.9)

 

C.  Replace  with  the  new  refrigerant  valve,  and  vacuumize  it,  and  refill  refrigerant,  complete  the 

replacement. 

 

 

Fig.8 

Summary of Contents for WI6225

Page 1: ...WI6225 Caple 60cm 2 Door Wine Cabinet Technical information...

Page 2: ......

Page 3: ......

Page 4: ...or 2 13 DG7 3 1 BH Evaporator fan 2 14 DG22 209 Air duct board 2 15 DG19 1 Fan cover 2 16 DG13 198 Senser cover 2 17 DG8 8 Senser 2 18 DG3 12 W LED Light 2 19 DG13 383 Display holder 2 20 DG20 256 Dis...

Page 5: ...le 60cm 2 Door Wine Cabinet 33 DG14 167 BL Lower hinge module Left 1 34 DG12 91 2 Condenser 1 35 DG13 6 11 Cabinet leg 4 36 DG12 113 Air circulating pipe 2 37 DG22 80 2 Compressor bracket 1 38 DG14 56...

Page 6: ......

Page 7: ...ry protection well When servicing the wine cooler with R600a systems please make sure the ambient is well ventilated Preparation before maintenance Tools 1 Plier 2 Cross screwdraver 3 Assistant pipe 4...

Page 8: ...cooler and check the current again check the discharge pipe of the compressor at the same time if it has an clear air pressure if the electricity is still too high or has not air pressure it shows th...

Page 9: ...pressure pipeline is on the process pipe of the filter Apply the vacuum pump for approximately 20 minutes Until the vacuum is lower than 100Pa Then solder the process pipe of the filter Keep the the s...

Page 10: ...ews need not to remove and remove the air duct board Be attention to unplug the connection wire when removing the air duct board You can move slowly aside until you can see the fans wire and unplug th...

Page 11: ...ant pipe soldered jointed B Anti dew pipe soldered joint C Right zone suction pipe soldered joint D Discharge pipe soldered joint E Left zone suction pipe soldered joint F Condenser soldered joint G F...

Page 12: ...the fan s fault the reason is following a The axletree of the fan broken b The bad balance because the fans abrasion 3 The fan can be replace with another same model s fan the procedure is following a...

Page 13: ...ency impact noise in capillary Zone Caused by either Causation 1 The capillary being insert too deep into the evaporator so when the refrigerant is Jetting the end of vibrating capillary will hit the...

Page 14: ...t fix for the door Fig 7 The instability of the wine cooler temperature The unstable temperature is caused by the evaporator fans cease and it can be check by the below method When the compressor is r...

Page 15: ...ion wire and the main board whether short circuit if not replace the sensor with the same module See Fig 8 6 The LED display shows HI and it is the high temperature protection indication After running...

Page 16: ...ht is normal and another zone is not cooling or over low temperature lower than the temperature preset 3 or one zone is not cooling the other zone is over cold please check the refrigerant valve 2 Tur...

Page 17: ...trical box in right zone disconnect all connectors remove the main PCB The process of display PCB removed remove the shelves take apart the inner electrical box disconnect all connectors if necessary...

Page 18: ...ers on display board supporter 8 as per arrowhead direction and then remove the display board and its two connectors from both sides Replace the display board See Fig 11 Fig 12 The name and explanatio...

Page 19: ...compressor 7 To the valve 8 To the main PCB white 9 To the condenser fan Red 10 To the transformer secondary How to remove the power PCB and transformer The process of power PCB removed remove the el...

Page 20: ...replace the LED light The process of LED light removed remove all shelve in the zone take apart the inner electrical box disconnect light connector if necessary remove the main PCB remove the LED ligh...