Installation Manual
Nov 2018 • Rev. 3.2
Introduction
The SmartLock
®
access control panel is a single door controller with inputs
for both entry and exit readers. Readers and card formats supported include
Cansec 37, 26 and 35-bit Corporate 1000 Wiegand formats, and Cansec
iButton
®
credentials. Other card formats can be accommodated with the use
of
Cansec Protocol Converters
(contact Cansec for further information).
SmartLock controllers with Pro Plus firmware (SLPPx.x) only work with
SmartLock Pro Plus software.
SmartLock controllers with Pro firmware (SLPTx.x) only work with
SmartLock Pro, SmartLock Managed Access and SmartLock Surf software.
The SmartLock control panel stores all cardholder data in non-volatile
memory to ensure continued operation and security in the event that
communications are lost to the host PC. Up to two control panels are easily
mounted in a SmartLock enclosure along with a Cansec 12 VDC power
supply and a back-up battery.
DIODES
Diodes are
required
for inductive loads such as electric strikes/locks. Failure
to use appropriate diodes will void the control panel warranty.
IMPORTANT:
In some jurisdictions, the use of a UL approved
power supply and connection to the fire alarm system for
emergency release may be required. Installers should contact the
local authority having jurisdiction to verify the specific
requirements. Also, a building permit may be required in some
jurisdictions for the installation of maglocks.