IMPORTANT
•
If the machine configuration has multiple PIMs or High Capacity stackers
attached, up to three PIMs can use one power strip or quad box that contains
separate 115V AC power outlets for each module (on the left side of the engine).
Up to three High Capacity stackers can use one power strip or quad box that
contains separate 115V AC power outlets for each module (on the right side of
the engine). The use of power strips or quad boxes also provides a power source
for service tools, such as a technician’s laptop computer or vacuum; however, it
is up to the customer to provide a separate 115V AC power source for this
purpose.
•
Use only dedicated and properly grounded outlets for the main unit. It is also
strongly suggested to use dedicated and properly grounded outlets for each
optional accessory. Do not use extension cords. The ground connection serves
to provide the internal electronics with a reference voltage. Faulty or poor ground
sources will cause this reference voltage to fall into a range that no longer serves
as a reliable reference voltage. The internal logic and programming of the
varioPRINT 6000 TITAN Series machines will not perform reliably because there
is an insufficient difference between the internal operating signal voltages and
the poor ground reference signal. A qualified electrician can measure and
provide the ground source that the varioPRINT 6000 TITAN Series machines or
any computer-controlled office equipment requires.
•
Before installation, confirm that all necessary receptacles are available.
NOTE
The power and dimension specifications for the PrintGuards or MEM should be
supplied between the print engine and HCS.