10 | Cannon Power Flue

REGULATORY LOCATION

MINIMUM CLEARANCES REQUIRED FOR BALANCED FLUE
TERMINALS, FAN ASSISTED FLUE TERMINALS, ROOM SEALED APPLIANCE
TERMINALS OR THE TERMINALS OF OUTDOOR APPLIANCES.

F

n

b

d

a

k

k

h

h

h

j

e

e

g

c

T

T

T

g

d

j

j

See note 2

See note 3

Openable
window

Door

I

P

M

T = Flue terminal                         M = Gas meter
I = Mechanical air inlet               P = Electricity meter or fuse box

Shading indicates prohibited
areas for flue terminals

Ref                                                                   Item

Minimum clearances

(mm)

Natural

draft

Fan

assisted

- unless appliance is certified for closer installation

Notes:
1 All distances are measured to the nearest part of the terminal.
2   Prohibited area below electricity meter or fuse box extends to ground level.
3   See clause 5.13.6.6 for restrictions on the flue terminal under covered areas.
4   See Appendix J. Figures J2(a) and J3(a), for clearances required from a flue terminal to an LP

Gas Cylinder. A flue terminal is considered to be a source of ignition.

5   For appliances not addressed above acceptance should be obtained from the technical regulator.

Special Note:

This chart MUST be read in-conjunction with
the full Australian Standard Gas Installations AS/NZS 5601.1

THE POWER FLUE HEATER IS FAN ASSISTED. SEE COLUMN HIGHLIGHTED

a               Below eaves, balconies and other projections:

Appliances up to 50 MJ/hr input                                                                       300                200
Appliances over 50 MJ/hr input                                                                        500                300

b               From the ground, above a balcony or other surface                                              300                300
c               From a return wall or external corner                                                                     500                500
d               From a gas meter (M)  (see 4.7.11 for vent location of regulator)                        1000              1000
e               From electricity meter or fuse box (P)                                                                    500                500
f                From a drain pipe or soil pipe                                                                                 150                  75
g               Horizontally from any building structure   or obstruction facing a terminal             500                500
h               From any other flue terminal, cowl, or combustion air intake                                 500                500
j                Horizontally from an openable window, door, non-mechanical air inlet or other opening into a

building with the exception of sub-floor ventilation:

Appliances up t 150 MJ/hr input                                                                       500                300
Appliances over 150 MJ/hr input up to 200 MJ/hr input                                 1500              1500
Appliances over 200 MJ/hr  input                                                                   1500              1500
All fan assisted flue appliances, in the direction of discharge                                              1500

k               From a mechanical air inlet, including a spa blower                                             1500              1500
n               Vertically below an openable window, non-mechanical air inlet, or any other opening into a building

with the exception of sub-floor ventilation:

Space heaters up to 50 MJ/hr input                                                                 150                150
Other appliances up to 50 MJ/hr                                                                      500                500

Appliances over 50 MJ/hr input and up to 150 MJ/hr input                            1000              1000
Appliances over 150 MJ/hr                                                                             1500              1500

FIG 5

Summary of Contents for Fitzroy FITZIB-PMEXx

Page 1: ...leave instruction manual with the owner Distributor This appliance is designed manufactured and distributed by Tel 1300 727 421 Models FITZIB PMEXx Models CANTIB PDEEx Fitzroy Canterbury x Colour Shar...

Page 2: ...ECIFICATIONS 8 CANTERBURY INBUILT POWER FLUE SPECIFICATIONS 9 REGULATORY LOCATOR 10 POWER FLUE INSTALLATION INSTRUCTIONS 11 14 FASCIA REMOVAL AND ELECTRICAL CONNECTION 15 LOG INSTALLATION GAS CONNECTI...

Page 3: ...in accordance with the manufacturer s instructions d will not cover faults due to normal wear and tear with reasonable use nor consumable components such as globes filters glass items etc e will not c...

Page 4: ...ng order Privacy The privacy of your personal information has always been important to us To learn more about how we collect keep and use your personal information please obtain a copy of our privacy...

Page 5: ...take care to avoid burns or clothing ignition This appliance is not intended for use by persons including children with reduced physical sensory or mental capabilities or lack of experience and knowle...

Page 6: ...AL turn the heater on again if there have been several attempts to ignite the heater without success If there is an interruption to the power supply the heater will fail safely and switch off When the...

Page 7: ...l lation options Install in a shallow recess or an existing fireplace elegant spacers will eliminate any size discrep ancies To enhance your Cannon s appearance add a decorative 3 or 4 sided surround...

Page 8: ...lator Integral part of controller Min inlet pressure 1 13 kPa NG 2 75 kPa Propane Fan 3 speed Ignition Electronic direct spark Power requirement 240V AC 10 Amp switch socket Power consumption 90 VA ma...

Page 9: ...r Integral part of controller Min inlet pressure 1 13 kPa NG 2 75 kPa Propane Fan 3 speed Ignition Electronic direct spark Power requirement 240V AC 10 Amp switch socket Power consumption 90 VA maximu...

Page 10: ...FLUE HEATER IS FAN ASSISTED SEE COLUMN HIGHLIGHTED a Below eaves balconies and other projections Appliances up to 50 MJ hr input 300 200 Appliances over 50 MJ hr input 500 300 b From the ground above...

Page 11: ...r or out through the terminal when installed horizontally The exhaust gas flue pipe must not trap and collect condensation This will adversely affect the performance of the heater POWER FLUE INSTALLAT...

Page 12: ...m lengths Place a liberal amount of silicon sealant to the inside of the flexible flue pipe which is to be mounted onto the flue exhaust outlet Slip the flexible aluminium hose over the flue exhaust...

Page 13: ...to seal the join and a hose clamp 3 Fit the PVC tubing and the air inlet to the other flexible tube using a hose clamp 4 Place terminal cover plate over both air intake and exhaust air pipes 5 Fit th...

Page 14: ...ving Canterbury Fascia To fully remove the fascia unclip the switch cable from the cable connector on the PCB and unclip the cable from the clipping points on the rear of the fascia Electrical Connect...

Page 15: ...d side of the heater at the bottom Refer FIG 26 2 With heater in position flanges should be hard against masonry Secure case flanges to the masonry Screw or bolt the flange through the slots provided...

Page 16: ...8 9 Turn clockwise to increase pressure and anti clockwise to decrease pressure FIG 32 Refer 5 Remove spanner and screwdriver Switch from BOOST to LOW to ensure settings are correct 6 Switch heater of...

Page 17: ...ion module 3 Lift ignition module from base panel 1 Remove the fascia Refer to page 14 of the installation manual 2 Disconnect the plugs on electronic controller Note Hook and loop mounting tape is us...

Page 18: ...hould be positioned in pointer 2 1 Remove the fascia Refer to page 14 of the installation instructions 2 Remove the electronic controller and ignition module Refer to page 17 3 Disconnect the fan plug...

Page 19: ...an is parallel to the top panel shown in Then remove the combustion fan making sure that it does not hit the male thread used to secure room circulation fan 9 Disconnect the electrical wiring off the...

Page 20: ...hin the allowed time Check the gas supply to the unit is not switched off Check the gas pressures Check the flame and spark electrode connections and that they are positioned correctly Ensure that the...

Page 21: ...the fan or check to see if air is blowing out of the flue pipe Check that the pressure tubes are connected correctly and not pinched or kinked The black tube should run from the black side of the pre...

Page 22: ...NOTES 22 Cannon Power Flue...

Page 23: ...Cannon Power Flue 23 NOTES...

Page 24: ...Certificate No Installed By COPY RATING LABEL HERE Don t Risk Your Appliance Warranty Only a licensed person will give you a compliance certificate showing that the work complies with all the relevan...

Reviews: