7
5. To increase the fan speed to MED, press switch for MED setting. Refer
figure 5.
6. To increase the fan speed to HIGH, press switch for HIGH setting.
Refer figure 6.
7. To turn the burner to LOW setting, press switch for LOW setting. Refer
figure 7.
On low burner setting it is more efficient to operate the fan speed on
LOW.
8. If the burner fails to ignite, wait 20 seconds and repeat the ignition
procedure. See below.
To turn burner OFF
To turn burner ON
9. In case of power failure return the switches to the OFF setting (refer
figure 2). When the power returns wait 20 seconds for any unburnt
gas to vent and start re-ignition as per point 3.
5
6
7
18
Alternative double skin flue installation
This heater is a flued appliance. It must be properly connected to a flue
system in accordance with the latest edition of the Gas Installation Code,
AS 5601.
If elbows are required, we recommend 45
°
only and no more than two in
the total flue run. There should also be a minimum of 250mm straight flue
section in between bends.
If practical locate the heater in a position to minimise the need for elbows.
There must be at least 1.8m of vertical before any changes in direction of
flue.
1. Ensure clearances to combustible have been observed. For clearances
refer page 10.
2. The centre line of the flue is 120mm to rear of appliance (excl. rear
spacers).
3. Carry out installation as per figure 27 (ceiling plate installation) and
figures 28 & 29 (flue installation).
Cut a hole 195 x 185mm in the ceiling in line with the flue position.
4. One large and two small holes in the bottom end of the lower outer flue
cover locate around the flue spigot and two locating pins. Refer figure
30.
Note: If the ceiling has an incline, the ceiling box will need to be fitted. The
ceiling box is an accessory and can be ordered from the supplier. Instal-
lation instructions are supplied with the ceiling box.
Alternative flue kit
The flue kit contains:
4 x 900mm lengths of 75mm ø inner galvanised flue.
1 x 850mm length of 170mm wide lower outer flue cover.
2 x 850mm length of 170mm wide upper flue cover.
1 x ceiling plate.
1 x 75mm AGA approved flue cowl.
Flue installation - Alternative double skin flue kit
27