C&S Electronics CSMPA22-2S Manual Download Page 4

1. Tunnel type mounting

Check if the relay  operate in overcurrent

Check the “TEST/RESET” button operation

Check if the wiring is correct (Refer to the wiring diagram).

Set the ‘D-time’ and ‘O-time’ knob to the min. ratings.

When the “TEST” button is pressed under tripped condition, the ‘O.L’ 
LED is turned off.
When you press the “TEST” button again then the lamp turned off and the 
relay reset.

 In operation, even though you press the “TEST/RESET” button, the 

relay do not trip.

2. Set the operating time (Definite time characteristics)

D-TIME (Delay time) : 0.2~30sec.
The  motor  starting  current,  which  flows  when  the  motor  is  starting,  is 

generally  600~800%  of  the  rated  current  and  the  delay  time  varies 
according to the load condition. It is the time during which the relay do not 
operate by over-current during the starting time.

Set the delay time by use of the ‘D-TIME’ knob.
In case you do not know the delay time, start the motor by setting the ‘D-
time’ knob to the max. position and after checking the time during which 
the starting current become stable, set the ‘D-TIME’ (In general pump, the 
setting time is 3-5 seconds)
Note : The time delay is forced time delay type, therefore if you make a 
mistake to select the time, the motor may burn.

The operating time is the time during which the relay tripped by the over-

current. The relay is tripped after the selected operating time.
Set the operation time by the ‘O-TIME’ knob.
In special case such as for mechanical shock relay, if you set the ‘O-TIME’ 
to the min value, the relay is tripped at once.

Generally set it to 4~6 seconds.

3. Set the operating current (Similar to that of the screw type)

Set the operation current to protect from over current. Set the current by 

considering the rated current

Start the motor by setting the ‘RC (A)’ knob to the maximum position.
Under  operating  condition,  rotate  the  ‘RC(A)’  knob  to  the 
counterclockwise until the ‘O.L’ LED turned on & off. The current at this 
point is the value (100%) under real load condition.
Rotate the ‘RC(A)’ knob to the clock-wise until the ‘O.L’ LED turned off. In 
general case the setting is 110~120% of the rated current.

4. Check the LED condition during the operation

Over current

The relay is not tripped during the ‘D-TIME’ under over-current but the 
O.L LED turned on and off to indicate that the over-current flows.
If the relay is tripped after ‘D-TIME’ the ‘O.L’ LED turned on.

Phase failure

If a motor does not rotate under phase failure, the high current may flow.
At this time a motor is protected by the over-current protection function.




n

n

n

n

n

n

Note :

Note : 

Operating & Setting of CSMPA-6OT

CSMPA - 60T

CSMPA - 60TE

TM

12

O-Time Knob

O.L LED

TEST/RESET Button

D-Time Knob

RC(A) Knob

O-Time Knob

O.L. LED

TEST/RESET  Button

RC(A) Knob

TM

Summary of Contents for CSMPA22-2S

Page 1: ...TM 40 26 Electronic Motor Protection Relays ...

Page 2: ...ry l l l Reverse phase l 3SR l 3SR l 3SR Current setting range A 0 3 1 5 1 5 4 4 22 Operating time characteristics Inverse time characteristics Inverse time characteristics CSMPA22 2PD Definite time Characteristics Time setting Inverse time 0 30 sec Sec Reset time Manual Reset Prompt Reset after 1min optional Tolerance Current 5 Time 5 or 0 5sec Control Voltage AC 100 260V Power Frequency 50 60Hz ...

Page 3: ...ent of a motor to protect from the over current Check if the rated current of a motor is within the current setting range of relay Set the RC A Rated current knob to the maximum value and then start a motor Under normal motor operation rotate the RC knob to the counterclockwise until the O L LED turned ON OFF The current at this point in the 100 current rating under real load At this point rotate ...

Page 4: ...ring which the relay tripped by the over current The relay is tripped after the selected operating time Set the operation time by the O TIME knob In special case such as for mechanical shock relay if you set the O TIME to the min value the relay is tripped at once Generally set it to 4 6 seconds 3 Set the operating current Similar to that of the screw type Set the operation current to protect from...

Page 5: ...LED External trip 2a Emergency Sequence ZCT Ratings 200mA 0 1mA Specification 25Æ 40Æ 80Æ Indication 7 segment 3 phase current Trip analysis setting indication LED Operation Trip System fail Communication Remote control Condition Self supervision System Fail LED Error indication Communication MODBUS RS 485 Installation Panel inside installation Door mounting Wlthdrawable cable Basic cable 2m Weigh...

Page 6: ...S 3SR With External Current Transformers CSMPA 22 40 80 2S 3S 3SR For Y D Wiring R S T MCCB MCD relay A1 95 97 A2 96 98 Relay FUSE TR MCM MCS 19T MCD 19X OFF RESET ON 19X MCD 19T 19X MCS MC MCM U V W M X Y Z MCS Note When you use the relay inside of the line apply the 1 3 value of the rated current MCM MCD MCS 19T 19X Magnetic Contactors for Power use Magnetic Contactors for motor operation use Ma...

Page 7: ...le 17 48 5 5 53 6 54 2 72 5 M3 5 8 52 63 50 5 44 23 7 48 7 2 012 u u u u u u u u u u u u u u u u u u u u 55 69 u u u u 47 u u u u 9 5 R2 5 05 62 5 1 5 22 u u u u u u u u u u u u 44 7 4 5 CSMPA 60T CSMPA 60TA CSMPA 22 2S CSMPA 80 2S CSMPA 22 3S CSMPA 80 3S CSMPA 22 3SR CSMPA 80 3SR 3 CT 100 400 500 600 CSMPA 40 2S CSMPA 40 3S CSMPA 40 3SR 8 INSERT M4 118 74 22 45 8 Ø5 5 62 5 141 51 141 118 74 14 5 ...

Page 8: ... 40 A 100 260 V 1a1b CSMPA80 2S 16 80 A 100 260 V 1a1b CSMPA80 3S 16 80 A 100 260 V 1a1b CSMPA80 3SR 16 80 A 100 260 V 1a1b CSMAP60 T 0 5 6 A 110 220 415 V 1c CSMPA60 T 5 60 A 110 220 415 V 1c CSMPA60 TE 0 5 6 A 110 220 V 1c CSMPA60 TE 5 60 A 110 220 V 1c Intellegent Motor Controller with communication Communication through Models RS 485 RS 422 Inverse Definite Time Characteristics Comprehensive D...

Page 9: ...We touch your everyday electricity 36 37 Sai Dham Commercial Center Landewadi Bhosari PUNE 411039 Email marketing genuineatuomation com Website www genuineautomation net GENUINE AUTOMATION ...

Reviews: