9. Troubleshooting
Reverse_DC
wrong DC polarity
1. Disconnect the AC first, then the DC switch,
and wait for five minutes, Unplug the reverse
connected string, Confirm the safety,
Re-make DC terminal, After confirming the
correct polarity, connect to the inverter.
Table 9.1 Fault message and description
DCinj-FAULT
High DC injection current
1. Check AC and DC connection.
2. Check inverter inside cable connection.
1. Restart inverter or contact installer.
Alarm Message
Failure description
Solution
ILeak-PRO
01/02/03/04
Leakage current protection
RelayChk-FAIL
Relay check fail
NOTE:
If the inverter displays any alarm message as listed in Table 9.1; please
turn off the inverter (refer to Section 5.2 to stop your inverter) and wait for 15
minutes before restarting it (refer to Section 5.1 to start your inverter). If the
failure persists, please contact your local distributor or the service center.
Please keep ready with you the following information before contacting us.
1. Serial number of Solis Three Phase Inverter;
2. The distributor/dealer of Solis Three Phase Inverter (if available);
3. Installation date.
4. The description of problem (i.e. the alarm message displayed on the LCD and the status
of the LED status indicator lights. Other readings obtained from the Information submenu
(refer to Section 6.2) will also be helpful.);
5. The PV array configuration (e.g. number of panels, capacity of panels, number of strings
, etc.);
6. Your contact details.
Reve-DC
One of the DC string is
reversely connected
1. Please check the inverters’ PV string polarity,
if there are strings reversely connected wait for
the night when the solar irradiance is low and the
PV string current down below 0.5A. Turn off the
two DC switchs and fix the polarity issue.
Screen OFF
with DC applied
Inverter internally damaged
1.Do not turn off the DC switches as it will
damage the inverter.
2.Please wait for the solar irradiance reduces
and confirm the string current is less than
0.5A with a clip-on ammeter and then turn
off the DC switches.
3.Please note that any damages due to wrong
operations are not covered in the device
warranty.
10. Specifications
.41.
.40.
Dimensions (W*H*D)
Weight
647*629*252mm
45kg
3/PE, 220
Max. DC input voltage (Volts)
MPPT voltage range (Volts)
Max. input current (Amps)
MPPT number/Max input strings number
Rated grid voltage (Volts)
Rated grid output current (Amps)
Max. output current (Amps)
Power Factor (at rated output power)
Max.efficiency
EU efficiency
Model
Topology
Self consumption (night)
Operating ambient temperature range
Relative humidity
Ingress protection
Cooling concept
Max.operation altitude
AC connection
Grid connection standard
DC connection
1100
3*26
3*40
3/6
0.8leading~0.8lagging
50/60
98.8%
98.3%
Transformerless
<
1W
-25
℃...
+60
℃
0~100%
Natural convection
4000m
Display
Communication connections
Warranty
Rated output power (Watts)
Max. output power (Watts)
Max. apparent output power (VA)
MC4 connector
OT Terminal (max 185 mm²)
LCD, 2×20 Z
RS485, Optional: Wifi, GPRS , PLC
5 years (extand to 20 years)
600
15000
15000
15000
39.4
43.3
THDi (at rated output power)
<3%
Start-up voltage (Volts)
Max short circuit input current (Amps)
Rated DC voltage (Volts)
Rated grid frequency (Hertz)
200...1000
180
En50549, G99, AS4777.2-2015, VDE0126-1-1,
IEC62727, VDE4105-2018, NB/T 32004, IEEE1547
CSI-15K-T220GL02-E
Safty/EMC standard
IEC62109-1/-2, EN61000-6-2,
EN61000-6-3, UL1741
IP65