6. Normal operation
6. Normal operation
Default Settings for Rule21 Standards:
Rated 480V Grid
V1:less than Vstart
V2 (Vstart): (221-304V) Default 293V
V3 (Vstop): (277-332V) Default 304V
V4: larger than Vstop
P1:100% P2:100% P3: 0% P4:0%
3. Volt-Var
Description: Inverter will change the reactive output power based on voltage change.
Q1
,
cap
Q2
=
Q3
=
0
Q4
,
ind
V1
V2
Vnom
V3
V4
Figure 6.28
Volt
-
VAR curve for Q
(
V
)
Default Settings for Rule21 Standard:
Q1: (0-60%) D30% Q4: (-60%-0%) Default -30%
Rated 480V Grid
V1:(221-277V) Default 254V V2: (221-304V) Default 268V
V3:(277-332V) Default 286V V4: (277-332V) Default 296V
Figure 6.29 Volt-VAR
Voltage1
:
254V
Voltage2
:
268V
4.Fixed-PF
Description: Inverter will output power with fixed power factor.
Setting Range: -0.8 to +0.8
Default value is PF = 1
.53.
.52.
5. Reac-power (Not Required)
Description: Inverter will generate reactive power based on changing output power.
Note: This Setting is NOT required by Rule21 Standards.
This function is for maintenance personnel only, wrong operation
will prevent the inverter from reaching maximum power.
6. P-factor (Not Required)
Description: Inverter will change power factor based on changing output power.
Note: This Setting is NOT required by Rule21 Standards.
This function is for maintenance personnel only, wrong operation
will prevent the inverter from reaching maximum power.
YES=<ENT> NO=<ESC>
Power
Factor
:+
1
.
00
Figure 6.30 Fixed-PF
Figure 6.31 PF Range
7.VgWatt-UL (Not Required)
Description: Inverter will change the active output power based on voltage change.
Note: This Setting is NOT required by Rule21 Standards.
This function is for maintenance personnel only, wrong operation
will prevent the inverter from reaching maximum power.