![CanadianSolar CSI-3K-S22002-E User Manual Download Page 14](http://html1.mh-extra.com/html/canadiansolar/csi-3k-s22002-e/csi-3k-s22002-e_user-manual_4075447014.webp)
6 Installation
10 / 30
≤15°
FIG.6-5 Installation Angle Requirements
13) Do not install the inverter outdoors in salt, sulfur or other corrosive areas.
The inverter would be corroded in salt (i.e. marine environments) area, and the corrosion
may cause fire. In salt area refers to the region within 500 meters from the coast.
Please consult the Canadian Solar Inc. Technical support department on the use of
inverters in special climates (i.e. salt, sulfur, or ammonia areas) which may affect the
product warranty.
6.2 Mounting Wall-mounting Bracket
Danger
To avoid electrical shock or other injury, please inspect existing
electronic or plumbing installations before drilling holes.
Installation steps:
1) Use the wall-mounting bracket as a template and mark the positions of the drill holes,
then drill the 4 holes accordingly, as per FIG. 6-6. (Diameter = 11mm, Depth ≥ 55mm
)
.
Note: The external dimensions (W × H) of inverters are shown as dash line in FIG. 6-6.
191
45
121
74
160
238
45
153
53
250
CSI-3K-S22002-E (308 x 357mm) CSI-5K-S22002-E (355 x 435mm)
FIG.6-6 Drilling Positions