background image

  | 

EN-Rev IM/GN-BM-EU/1.8 Copyright ©  March, 2021. CSI Solar Co., Ltd.

 

www.csisolar.com

 

box provided may vary depending on the model series. 

 

Only connect the quantity of modules that corresponds 
to the voltage specifications of the inverters used in the 
system.  In  addition,  modules  must  not  be  connected 
together to create a voltage higher than the maximum 
permitted  system  voltage  stated  on  the  module 
nameplate,  even  under  the  worst  local  temperature 
conditions  (see  Table  1  for  the  correction  coefficients 
that apply to open-circuit voltage).     

 

A maximum of two strings can be connected in parallel 
without using an over-current protection device (fuses, 
etc.) incorporated in series within each string. Three or 
more  strings  can  be  connected  in  parallel  if  an 
appropriate  and  certified  over-current  protection 
device  is  installed  in  series  within  each  string.  And  it 
shall  be  ensured  in  the  PV  system  design  that  the 
reverse current of any particular string is lower than the 
module maximum fuse rating at any circumstances. 

 

Only modules with similar electrical parameters should 
be connected in the same string to avoid or minimize 
mismatch effects in arrays. 

 

To  minimize  risk  in  the  event  of  an  indirect  lightning 
strike,  avoid  forming  loops  with  the  wiring  when 
designing the system. 

 

The  recommended  maximum  series  fuse  rating  is 
stated in a table in the Annex A. 

 

Modules  should  be  safely  fixed  to  bear  all  expected 
loads, including wind and snow loads.   

 

After the installation of double glass modules, a 30 mm 
deflection for framed module is allowed. 

 

For framed modules, a minimum clearance of 6.5 mm 
(0.25 in) between modules is required to allow thermal 
expansion of the frames and modules. 

OPTIMUM ORIENTATION AND TILT 

 

To  maximize  the  annual  yield,  please  calculate  the 
optimum  orientation  and  tilt  for  PV  modules  in  that 
specific installation site. The highest yields are achieved 
when  sunlight  shines  perpendicularly  onto  the  PV 
modules. 

AVOID SHADING 

 

Even  minor  partial  shading  (e.g.  from  dirt  deposits) 
reduces  yields.  A  module  can  be  considered  to  be 
unshaded if its entire surface is free from shading all 
year round. Sunlight should be able to reach at least the 
module even on the shortest day of the year. 

 

For optimizing the power generation of the rear side of 
bifacial modules, obstacles between modules and the 
mounting  ground  should  be  avoided  as  much  as 
possible 

 

Constant shading conditions can affect module service 
lifetime, due to accelerated ageing of the encapsulation 
material and thermal stress on the bypass diodes.   

RELIABLE VENTILATION 

 

Bifacial  modules  use  direct,  reflected,  or  diffuse 
sunlight on the backside to generate additional power. 
Therefore,  bifacial  modules  are  not  suggested  to  be 
used in building attached photovoltaic systems (BAPV). 
If BAPV, or similar mounting is still required, sufficient 
clearance of at least 10 cm (3.94 in) between the module 
and the mounting surface needs to be provided to allow 
cooling air to circulate around the back of the module. 
This also allows condensation or moisture to dissipate. 

 

According  to  UL  1703,  any  other  specific  clearance 
required  for  maintaining  a  system  fire  rating  should 
prevail. Detailed clearance requirements pertaining to 
system fire ratings must be provided by your racking 
supplier. 

5.1 MODULE WIRING 

CORRECT WIRING SCHEME 

 

Ensure that the wiring is correct before starting up the 
system. If the measured open circuit voltage (Voc) and 
short-circuit current (Isc) differ from the specifications, 
this indicates that there is a wiring fault. 

 

When modules have been pre-installed, but the system 
has not been connected to the grid yet, each module 
string should be kept under open-circuit conditions and 
proper  actions  should  be  taken  to  avoid  dust  and 
moisture penetration inside the connectors. 

 

Do not connect different connectors (brand and model) 
together.   

Summary of Contents for CS3K-265PB- AG

Page 1: ...For professional use only INSTALLATION MANUAL OF BIFACIAL MODULE...

Page 2: ...CHANICAL ELECTRICAL SPECIFICATIONS 4 4 0 UNPACKING AND STORAGE 5 5 0 MODULE INSTALLATION 6 5 1 MODULE WIRING 8 5 2 GROUNDING 11 6 0 MOUNTING INSTRUCTIONS 12 6 1 MOUNTING METHODS FOR FRAMED BIFACIAL MO...

Page 3: ...sis 1 2 LIMITATION OF LIABILITY Canadian Solar shall not be held responsible for damages of any kind including without limitation bodily harm injury or damage to property in connection with handling P...

Page 4: ...ration above 0 1 weight by weight The copper ribbons used in our solar modules to interconnect solar cells use a thin solder coating layer that contains lead CAS no 7439 92 1 Under normal or reasonabl...

Page 5: ...ing fuse rating The maximum string fuse ratings can be found in ANNEX A Mechanical and Electrical Ratings for all the certified Canadian Solar bifacial module types The minimum string fuse rating for...

Page 6: ...Do not stand step walk and or jump on modules under any circumstances Localized heavy loads may cause severe micro cracks at cell level which in turn may compromise module reliability and void Canadi...

Page 7: ...nditions Part 2 1 Environmental conditions appearing in nature Temperature and humidity Please consult the Canadian Solar technical support department for more information on the use of modules in spe...

Page 8: ...hat specific installation site The highest yields are achieved when sunlight shines perpendicularly onto the PV modules AVOID SHADING Even minor partial shading e g from dirt deposits reduces yields A...

Page 9: ...e In case where a cable connection method not included in below table is used please confirm suitable cable length with Canadian Solar s sales representative Table 2 System Cable Scheme for CS3W CS3U...

Page 10: ...1400 mm jumper cable CS3Y CS6W Cable length 410 mm 290 mm 2000 mm jumper cable Note Modules in adjacent rows need to be rotated 180 degrees for proper installation Portrait installation one row Leap...

Page 11: ...resistant cable ties Protect exposed cables from damage by taking appropriate precautions e g placing them inside a metallic raceway like EMT conduit Avoid exposure to direct sunlight A minimum bendi...

Page 12: ...mplying with UL 1703 or UL 61730 and IEC 61215 2 2016 a safety factor of 1 5 should be applied for calculating the equivalent maximum authorized design loads Project design loads depend on constructio...

Page 13: ...bolt length should be chosen based on actual module frame height For bifacial module with 30 mm frame height our recommended maximum bolt length is 20 mm in order to properly insert the bolts through...

Page 14: ...four holes installation method B Installation Method Module Types Inner four holes installation method A Inner four holes installation method B Middle four holes installation method A Middle four hol...

Page 15: ...of support structure The mounting rails shall be designed to limit as much as possible shade on module rear side cells Canadian Solar s warranty may be void in cases where improper clamps or unsuitabl...

Page 16: ...frame Module Types Max Mechanical Load Pa 3600 2400 5400 2400 5400 3600 A Range mm CS3K 270 380 CS3U 410 490 CS3W 410 490 CS3Y 300 600 400 550 CS6W 300 600 400 500 6 2 2 Clamp mounting on short side o...

Page 17: ...Co Ltd www csisolar com 6 2 3 Clamp mounting on long side of frame and rails parallel to the long side frame Module Types Max Mechanical Load Pa 3800 3200 4000 3200 4400 3200 4400 3600 A1 Range mm CS3...

Page 18: ...an Solar technical support department in writing for advice Tracker 1P Bolting method Install and tighten the module clamps to the mounting rails using the torque stated by the mounting hardware manuf...

Page 19: ...0 1800 600 80 2400 2400 Tracker 2P Bolting method Module type Mounting hole space mm Mounting hole location Plain washer outer diameter mm Test load Pa CS3W PB AG CS3W MB AG A1 A3 400 B1 B3 1155 B1 B2...

Page 20: ...tial electric shock hazard Cracked or broken modules represent an electric shock hazard due to leakage currents and the risk of shock is increased when modules are wet Before cleaning thoroughly inspe...

Page 21: ...S Method A Compressed Air Canadian Solar recommends cleaning the soft dirt like dust on modules just with air pressure This technique can be applied as long as the method is efficient enough consideri...

Page 22: ...93 25 CS3U 380MB AG 380 40 0 9 50 47 8 10 01 25 CS3U 385MB AG 385 40 2 9 58 48 0 10 09 25 CS3U 390MB AG 390 40 4 9 66 48 2 10 17 25 CS3U 395MB AG 395 40 6 9 73 48 4 10 25 25 CS3U 400MB AG 400 40 8 9 8...

Page 23: ...31 2 8 98 37 9 9 47 25 CS3K 285PB AG 285 31 4 9 08 38 1 9 56 25 CS3K 290PB AG 290 32 3 8 98 38 9 9 49 25 CS3K 295PB AG 295 32 5 9 08 39 1 9 57 25 CS3K 300PB AG 300 32 7 9 18 39 3 9 65 25 CS3K 305PB AG...

Page 24: ...9 11 71 25 CS3W 460MB AG 460 40 9 11 25 49 1 11 77 25 CS3W 465MB AG 465 41 1 11 32 49 3 11 83 25 CS3Y 465MB AG 465 43 6 10 67 52 3 11 42 25 2260 x 1048 x 32 89 0 x 41 3 x 1 26 in 29 9 65 9 lbs CS3Y 4...

Page 25: ...n Circuit Voltage Voc V Short Circuit Current Isc A Max Series Fuse Rating A Overall Dimension mm Weight Kg CS6W 530MB AG 530 40 9 12 96 48 8 13 80 30 CS6W 535MB AG 535 41 1 13 02 49 0 13 85 30 CS6W 5...

Page 26: ...019 Rev 1 3 is released in September 2019 Rev 1 4 is released in December 2019 Rev 1 4 is released in December 2019 Rev 1 5 is released in April 2020 Rev 1 6 is released in May 2020 Rev 1 7 is release...

Reviews: