![Camus Hydronics DRW1000 Installation And Service Manual Download Page 57](http://html1.mh-extra.com/html/camus-hydronics/drw1000/drw1000_installation-and-service-manual_490912057.webp)
57
Table 16: Lockout Codes
#
Description
1
Unconfigured safety data
2
Waiting for safety data verification
3-46
Internal Fault. Replace SOLA Controller
47
Flame rod to ground leakage
48
Static Flame
49
24VAC low/high
50
Modulation Fault
64
Fan speed not proved, ignition failure
67
Interlock Off, safety circuit is open
79
Heater Outlet high limit tripped
81
Delta T Limit
82
Stack limit tripped (PVC: 149
o
F, CPVC: 194
o
F,
250
o
F)
91
Inlet sensor fault
92
Outlet sensor fault
93
DHW sensor fault
94
Header sensor fault
95
Stack sensor fault
96
Outdoor sensor fault
105
Flame detected out of sequence
106
Flame lost if Main Flame Establishing Period
(MFEP)
107
Flame lost early in run
108
Flame lost in run
109,
110
Ignition failed
112
Pilot test flame timeout
113
Flame circuit timeout
149
Flame detected
* If an internal hardware error is detected contact Camus®
technical support for troubleshooting procedure.
Table 17: Alert/Hold Codes
#
Description
29
Burner switch turned OFF
30
Burner switch turned ON
47
Invalid subsystem request occurred
50
Modulation Fault (DR300 – 1000 ONLY)
54-56 Processor brown-out.
61
Anti-short Cycle
62
Fan speed not proved
63
LCI off, safety circuit is open
68
Setpoint was overridden due to sensor fault
69
Modulation was overridden due to sensor fault
123
Modulation rate was limited due to outlet limit
124
Modulation rate was limited due to Delta-T limit
215
No Lead Lag slaves available to service demand
219
Using backup Lead Lag header sensor due to
sensor failure
229
Lead lag slave communication timeout.
275-
281
LCI off, safety circuit is open
283
Demand off during measured purge time
291
Abnormal Recycle: Flame was not on at end of
Ignition period
292
Abnormal Recycle: Flame was lost during Main
Flame Establishing Period
293
Abnormal Recycle: Flame was lost early in Run
294
Abnormal Recycle: Flame was lost during Run
303-
310
+
Interlock Off, safety circuit is open
324,
374-
379
Hardware flame bias. Flame sensor wire needs to
be re-routed.
352
+
Stack sensor fault
355
+
Outlet sensor fault
357
+
DHW sensor fault
359
+
Inlet sensor fault
460
LCI lost in run
550
Delta T inlet/outlet limit was exceeded
+
The alarm LED and alarm contacts are closed and will remain
closed until the ‘RESET’ button is pressed.
Summary of Contents for DRW1000
Page 2: ...99 0171 REV 0 9...
Page 35: ...35...
Page 48: ...48...
Page 67: ...67 PART 12 EXPLODED VIEW 19 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 20...
Page 68: ...68 21 22 23 24 26 35 34 33 32 31 30 29 28 27 25 36 37 38 39 40 42 43 56...
Page 75: ...75 PART 13 ELECTRICAL DIAGRAMS...
Page 76: ...76...
Page 77: ...77...
Page 78: ...78...
Page 79: ...79...