35
6.9
MODE 4 & 5: OUTDOOR RESET OPERATION: VIEW DISPLAY
From the Home display;
1) Press [ITEM] to view the following parameters:
Display
Parameter
Name
Parameter Description
Parameter
Range
Outdoor
Temperature
Real-time Outdoor Temperature
-60 to 190
o
F
(-51 to 88
o
C)
Boiler Target
Temperature
To provide a target setpoint for the
heating system. Setpoint is controlled
to the inlet sensor
---, 35 to 266
o
F
(---, 2 to 130
o
C)
System
Temperature
System Temperature of Primary Loop
NOTE: This parameter is only
available in Mode 5
14 to 266
o
F
(-10
to 130
o
C)
Boiler Outlet
Temperature
Real-time Outlet Temperature
14 to 266
o
F
(-10
to 130
o
C)
Boiler Inlet
Temperature
Real-time Inlet Temperature
14 to 266
o
F
(-10
to 130
o
C)
Boiler Delta
T
Real-time temperature difference
between the outlet sensor and the inlet
sensor.
-99 to 252
o
F
(-72 to 122
o
C)
Modulation
Real-time modulating output
percentage
0 to 100%
Total Run
Time Since
Installation
Monitors the amount of operational
time since the MicoFlame was
installed. The first two digits are the
number of thousands of hours and the
three digit display shows the number
of hundreds of hours.
Press
simultaneously to reset
the counter
Alternates
between 00 and
999
Summary of Contents for DFH1100
Page 2: ......
Page 12: ...7 Table 4 Appliance Dimensions and Specifications Table 5 Vent Sizes for a Single Appliance...
Page 58: ...53 PART 12 EXPLODED VIEW...
Page 59: ...54...
Page 60: ...55...
Page 66: ...61 PART 13 ELECTRICAL DIAGRAMS...
Page 67: ...62...
Page 68: ...63 Camus DynaFlame PCB Electrical Ladder Diagram...