CPS-EX3000 MANUAL
Camtec Power Supplies GmbH - Gewerbestrasse 30 - DE-76327 Pfinztal / Germany
P.7/21 (07/2017.01.3)
Tel. +49 (721) 46596 - 0 Fax +49 (721) 46596 - 77
www.camtec-gmbh.com
-
(Subject to alterations. This product is not designed to be used in applications such as life support systems wherein a failure or malfunction could result in injury or death)
CON1
Push In
0,14-
1,5mm²
AWG26-16
CON2
CON3
CON4
DC +/-
M8
200A/60°C
250Vac
20A
Neutrik
PowerCon®
3x2,5 mm²
Neutrik NAC3FCA
Copy of the original instruction:
http://www.neutrik.com/de/powercon/powercon-20-a/nac3fca
- Interface pluggable Push-Pull-Connectors from Weidmueller (included)
- Input Power Connector Neutrik NAC3FCA (included)
- Output Power Connection M8 Powerbars
- Lock-Pins snap into the 2U/3U 19“-subrack
WARNING
OUTPUT CONNECTION INSTRUCTION:
Mount the cable lugs directly on the output terminals followed by a washer, a split washer and a
screw.
Failure to follow the order can result in excessive heat! Recommended torque: 8-10Nm. Use
only screws, washers and split washers supplied with this unit.