Appendix C. Monitoring Sampler Status via RS-485
C-2
4. Click the
MD485
tab. Select
CS I/O
and
RS-485
in the
Active Ports
box.
Select
Transparent Communication
in the
Protocol Configuration
box
FIGURE C-2. MD485 Deployment tab
5. Click the
CS I/O
tab. Set the mode based on the type of datalogger being
used.
a. The shown configuration is for a CR1000. We used SDC7 for the
address.
6. Click the
RS-485
tab. Set
Baud Rate
to
38.4k
. Set
Parity
to
None
. Set
Character Length
to
8 bits
. Set
Stop Bits
to
1 bit
FIGURE C-3. MD485 RS-485 tab
7. Click
Apply
.
Summary of Contents for PVS5120 Series
Page 2: ......
Page 4: ......
Page 6: ......
Page 8: ......
Page 70: ...Appendix A Sample Transport Velocity A 2...
Page 78: ...Appendix B Example Programs B 8...
Page 86: ...Appendix C Monitoring Sampler Status via RS 485 C 8...
Page 96: ...Appendix G Generic Modbus Control G 4...
Page 100: ...Appendix H ISO5667 Conformity H 4...
Page 101: ......