CS15-L Current Transformer
1. General Description
The CS15-L uses a modified CR Magnetic’s CR8459 Current Transformer to
measure the approximate current over a range of 0 to 125 A. The CS15-L
outputs a millivolt signal allowing it to be directly connected to the CR2XX
dataloggers. The CS15-L is recommended for measurements that do not
require high accuracy.
FIGURE 1. CS15-L Current Transformer
2. Specifications
Example Applications:
•
Motor or generator load conditions
•
Efficiency studies
•
Intermittent fault detection
•
Rough submetering
Manufacturer’s Specifications
Frequency:
50 and 60 Hz
Insulation Resistance:
100 M ohm @ 500 VDC
High Potential:
2000
volts
Rated Current:
125
A
Storage Temperature:
-25
º
C to 70
º
C
Operating Temperature:
-25
º
C to 55
º
C
Case Material:
Polypropylene
Resin
Construction:
Epoxy
Encapsulated
Accuracy with 10 ohm
burden max. (resistive):
typically
±
5 percent of actual value with
provided
multiplier
Dimensions:
Outer diameter: 1.89” (4.8 cm)
Inner diameter: 0.75” (1.9 cm)
Depth:
0.67” (1.7 cm)
1