Section 8. Operation
388
3.
PakBus
(p. 77)
commands — the CR800 is a PakBus device, so it is capable of
being a node in a PakBus network. Node clocks in a PakBus network are
synchronized using the
SendGetVariable()
,
ClockReport()
, or
PakBusClock()
commands. The CR800 clock has a resolution of 10 ms,
which is the resolution used by PakBus clock-sync functions. In networks
without routers, repeaters, or retries, the communication time will cause an
additional error (typically a few 10s of milliseconds). PakBus clock
commands set the time at the end of a scan to minimize the chance of skipping
a record to a data table. This is not the same clock check process used by
LoggerNet
as it does not use average round trip calculations to try to account
for network connection latency.
4. Radios — A PakBus enabled radio network has an advantage over Ethernet in
that
ClockReport()
can be broadcast to all dataloggers in the network
simultaneously. Each will set its clock with a single PakBus broadcast from
the master. Each datalogger in the network must be programmed with a
PakBusClock()
instruction.
Note
Use of PakBus clock functions re-synchronizes the
Scan()
instruction. Use should not exceed once per minute. CR800 clocks drift at
a slow enough rate that a
ClockReport()
once per minute should be
sufficient to keep clocks within 30 ms of each other.
With any synchronization method, care should be taken as to when and
how things are executed. Nudging the clock can cause skipped scans or
skipped records if the change is made at the wrong time or changed by
too much.
5. GPS — clocks in CR800s can be synchronized to within about 10 ms of each
other using the
GPS()
instruction. CR800s built since October of 2008 (serial
numbers ≥ [7920] ) can be synchronized within a
few microseconds of each
other and within ≈200 µs of UTC. While a GPS signal is available, the CR800
essentially uses the GPS as its continuous clock source, so the chances of
jumps in system time and skipped records are minimized.
6. Ethernet — any CR800 with a network connection (internet, GPRS, private
network) can synchronize its clock relative to Coordinated Universal Time
(UTC) using the
NetworkTimeProtocol()
instruction. Precisions are usually
maintained to within 10 ms. The NTP server could be another logger or any
NTP server (such as an email server or nist.gov). Try to use a local server —
something where communication latency is low, or, at least, consistent. Also,
try not to execute the
NetworkTimeProtocol()
at the top of a scan; try to ask
for the server time between even seconds.
8.2
Switched-Voltage Output — Details
Related Topics:
• Switched Voltage Output — Specifications
•
Switched Voltage Output — Overview
(p. 59)
•
Switched Voltage Output — Details
(p. 388)
•
Current Source and Sink Limits
(p. 389)
•
PLC Control — Overview
(p. 87)
Summary of Contents for CR800 Series
Page 2: ......
Page 4: ......
Page 6: ......
Page 32: ......
Page 34: ......
Page 54: ......
Page 92: ......
Page 310: ......
Page 446: ...Section 8 Operation 446 8 11 2 Data Display FIGURE 100 CR1000KD Displaying Data ...
Page 448: ...Section 8 Operation 448 FIGURE 102 CR1000KD Real Time Custom ...
Page 449: ...Section 8 Operation 449 8 11 2 3 Final Storage Data FIGURE 103 CR1000KD Final Storage Data ...
Page 450: ...Section 8 Operation 450 8 11 3 Run Stop Program FIGURE 104 CR1000KD Run Stop Program ...
Page 452: ...Section 8 Operation 452 FIGURE 106 CR1000KD File Edit ...
Page 456: ......
Page 462: ......
Page 523: ...Section 11 Glossary 523 FIGURE 116 Relationships of Accuracy Precision and Resolution ...
Page 524: ......
Page 526: ......
Page 556: ......
Page 558: ......
Page 560: ......
Page 597: ......