Section 7. Installation
182
Use of Multiple Scans
'This program example demonstrates the use of multiple scans. Some applications require
'measurements or processing to occur at an interval different from that of the main
'program scan. Secondary scans are preceded with the SlowSequence instruction.
'Declare Public Variables
Public
PTemp
Public
Counter1
'Declare Data Table 1
DataTable
(DataTable1,1,-1)
'DataTable1 is event driven.
'The event is the scan.
Sample
(1,PTemp,FP2)
Sample
(1, Counter1, fp2)
EndTable
'Main Program
BeginProg
'Begin executable section of program
Scan
(1,Sec,0,0)
'Begin main scan
PanelTemp
(PTemp,250)
Counter1 = Co 1
CallTable
DataTable1
'Call DataTable1
NextScan
'End main scan
SlowSequence
'Begin slow sequence
'Declare Public Variables for Secondary Scan (can be declared at head of program)
Public
Batt_Volt
Public
Counter2
'Declare Data Table
DataTable
(DataTable2,1,-1)
'DataTable2 is event driven.
'The event is the scan.
Sample
(1,Batt_Volt,FP2)
Sample
(1,Counter2,FP2)
EndTable
Scan
(5,Sec,0,0)
'Begin 1st secondary scan
Counter2 = Co 1
Battery
(Batt_Volt)
CallTable
DataTable2
'Call DataTable2
NextScan
'End slow sequence scan
EndProg
'End executable section of program
7.7.2 Data Input: Loading Large Data Sets
Large data sets like look-up tables or tag numbers, can be loaded in the CR800 for
use by the CRBasic program. Do this by using the
Data
,
DataLong
, and
Read
instructions, as demonstrated in CRBasic example
Loading Large Data Sets
(p. 182).
Summary of Contents for CR800 Series
Page 2: ......
Page 4: ......
Page 6: ......
Page 32: ......
Page 34: ......
Page 54: ......
Page 92: ......
Page 310: ......
Page 446: ...Section 8 Operation 446 8 11 2 Data Display FIGURE 100 CR1000KD Displaying Data ...
Page 448: ...Section 8 Operation 448 FIGURE 102 CR1000KD Real Time Custom ...
Page 449: ...Section 8 Operation 449 8 11 2 3 Final Storage Data FIGURE 103 CR1000KD Final Storage Data ...
Page 450: ...Section 8 Operation 450 8 11 3 Run Stop Program FIGURE 104 CR1000KD Run Stop Program ...
Page 452: ...Section 8 Operation 452 FIGURE 106 CR1000KD File Edit ...
Page 456: ......
Page 462: ......
Page 523: ...Section 11 Glossary 523 FIGURE 116 Relationships of Accuracy Precision and Resolution ...
Page 524: ......
Page 526: ......
Page 556: ......
Page 558: ......
Page 560: ......
Page 597: ......