SECTION 1. FUNCTIONAL MODES
1-7
TABLE 1.7-1. *C Mode Entries and Codes
Key
Display
Entry
ID: Data
Description
*C
12:0000
Enter current password.
If correct, then advance,
else exit *C Mode. 12:00
indicates *C Mode is not
in PROMs. If security is
disabled, *C advances
directly to window 1.
A
01:00
Window 1, enter
command:
00 = disable security and
advance to window
2; subsequent *0 or
*6 enables security.
01 = security remains
enabled, but it
advances to window
2 and allows entry of
a new password.
A
02:XXXX
Set new password
(XXXX is current
password).
A
Returns to window 1.
Entering 0000 disables
security (window 1 must
be set to 0).
1.8 *D MODE -- SAVE OR LOAD
PROGRAM
The *D Mode allows the user's program
information in the *1, *2, *3, *4, *A, *C (if OSX-
0), and *B Modes to be output to or loaded from
printer/computer (ASCII) or SM192/716 Storage
Module. Table execution and on-line printer
outputs are suspended while in the *D Mode.
When
*D
is keyed, the CR7 will display "13:00".
TABLE 1.8-1. *D Mode Commands
Command
Description
1
Save ASCII Program
2
Load ASCII Program
71
Save/Load/Clear Program
from Storage Module
A command is entered by keying the command
number and
A
. When Command 1, 2, or 71 is
entered, the command number is displayed in
the ID field. The user must then key in a baud
rate code for command 1 or 2 or the command
code for the Storage Module (Table 1.8-2).
After the code is keyed in, key
A
to execute the
command. After a command is executed,
"13:0000" is displayed;
*D
must be entered
again before another command can be given.
If the CR7 program has not been compiled
when a command to save the program is
entered, it will be compiled before the command
is executed.
TABLE 1.8-2. *D Mode Baud Rate and
Storage Module Codes
BAUD RATE
STORAGE MODULE
CODES
COMMAND CODES
0 - 300 baud
1X Save Program X to
1 - 1200
Storage Module
2 - 9600
(X=1-8)
3 - 76,800
2X Load Program X from
Storage Module
(X=1-8)
3X Erase Program X from
Storage Module
(X=1-8)
Summary of Contents for CR7
Page 2: ...This is a blank page ...
Page 4: ...This is a blank page ...
Page 28: ...CR7 MEASUREMENT AND CONTROL SYSTEM OVERVIEW OV 18 This is a blank page ...
Page 38: ...SECTION 1 FUNCTIONAL MODES 1 10 This is a blank page ...
Page 42: ...SECTION 2 INTERNAL DATA STORAGE 2 4 This is a blank page ...
Page 52: ...SECTION 3 INSTRUCTION SET BASICS 3 10 This is a blank page ...
Page 58: ...SECTION 4 EXTERNAL STORAGE PERIPHERALS 4 6 This is a blank page ...
Page 68: ...SECTION 6 9 PIN SERIAL INPUT OUTPUT 6 6 This is a blank page ...
Page 140: ...SECTION 13 CR7 MEASUREMENTS 13 16 FIGURE 13 5 1 Circuits Used with Instructions 4 9 ...
Page 162: ...APPENDIX A GLOSSARY A 4 This is a blank page ...
Page 164: ...B 2 This is a blank page ...
Page 170: ...APPENDIX C BINARY TELECOMMUNICATIONS C 6 This is a blank page ...
Page 174: ...APPENDIX D CALIBRATION PROCEDURES D 4 FIGURE D 2 2 CR7X CPU Card ...