10. (Optional) In this mode, an Automated Power Schedule can be setup to save on battery life
or on cellular charges. Go to the Settings then Serial Mode Setup tab. Enter a Start (power-
on) Time, On Duration, and Repeat Cycle.
For example: With the following settings of Start (power-on) Time of 22:00, On Duration of
10 minutes, and Repeat Cycle of Every Hour the cellular module will turn on for ten minutes
only twice each day. It will turn on at 10:00 pm and 11:00 pm. It will not turn on at midnight
since it is powered off at the start of the next day.
6.4.4.2 Configure data logger (optional)
SendVariables()
is used to initiate a data logger call-back attempt to a computer running
LoggerNet. It has the following syntax:
SendVariables
(ResultCode, ComPort, NeighborAddr, PakBusAddr, Security, TimeOut,
"TableName", "FieldName", Variable, Swath )
The
ComPort
needs to be set to ComRS232 or ComSDC8 depending on how you have the
module connected to the data logger. Set the
TableName
to "Public" and the
FieldName
CELL200-Series 4G LTE Cellular Module