CDM-A100 Series
15
Current Excitation
Range:
±2.5 mA
Accuracy
1
0 to 40 °C:
±(0.05% of s 2.5 µA)
–40 to 70 °C:
±(0.08% of s 2.5 µA)
–55 to 85 °C:
±(0.1% of s 2.5 µA)
Resolution:
638 nA
Compliance Voltage
2
:
±5000 mV
1
Note that ratiometric accuracy, rather than absolute accuracy, determines overall
measurement accuracy of ratiometric-resistance measurements.
2
Voltage limits within which current excitation setting will meet specified accuracy
limits.
6.4 Period Averaging – Specifications
Terminals
CDM-A108:
SE 1 – 16
CDM-A116:
SE 1 – 32
Range:
Accuracy:
±(0.01% of r resolution)
Resolution:
130 ns ÷ number of cycles
TABLE 6-3. Period Average Ranges
Voltage Gain
Minimum
Peak-to-Peak
Signal
1,2
(mV)
Minimum Pulse
Width
(µs)
Maximum
Frequency
(kHz)
1
500
2.4
200
3.8
50
8
50
19
10
50
8
67
2
80
5
1
With signal centered around CDM-A100 ground.
2
Maximum period average signal amplitude = 20 V peak-to-peak.
6.5 Voltage Output – Specifications
6.5.1 Continuous 12 Vdc
Terminals
CDM-A108:
12V
CDM-A116:
12V
Voltage Output
1
:
12.5 ± 0.5 Vdc