6.3 Wind sentry assembly
Operating temperature: –50 to 50 °C assuming non-riming conditions
Overall height:
32 cm (12.6 in)
Crossarm length:
40 cm (15.7 in) between instruments (center-to-center)
Mounting diameter:
34 mm (1.34 in), mounts on standard 1 inch IPS pipe
7. Installation
If you are programming your data logger with
Short Cut
, skip
(p. 7) and
Short Cut
does this work for you. See
(p. 2) for a
Short Cut
tutorial.
7.1 Wiring
Connections to CRBasic data loggers are given in
(p. 8), and
(p. 8). When
Short Cut
software is used to create the data logger program, the sensor is wired to
the terminals shown in the wiring diagram created by
Short Cut
.
Table 7-1: 03002 Wind Sentry Set wire color, wire function, and data logger connection
Wire color
Wire function
Data logger connection terminal
Red
WS signal
U configured for pulse input
1
, P (pulse input),
or P_LL (pulse, low-level ac)
Black
WS signal reference
⏚
Green
WD signal
U configured for single-ended analog input
1
,
SE (single-ended, analog input)
Blue
WD voltage excitation
U configured for voltage excitation
1
, EX,
or VX (voltage excitation)
White
WD signal reference
⏚
(analog ground)
Clear
Shield
⏚
(analog ground)
1
U terminals are automatically configured by the measurement instruction.
Wind Sentry Series