Operation and maintenance instructions
Series PRE proportional pressure regulator
IO-Link version
5000030186
Ver. 03
32
13.2.10.
Pressure regulation check mode
Sets the type of event triggered by the
“pressure regulation check”, 129 = warning o
r 10 = error.
This check uses the same window as the window control with the difference that the pressure
reading must remain outside the window for a time defined by the
“Pressure regulation
timeout”
parameter.
13.2.11.
Pid mode
•
Set the PID gains, the values it can take are:
•
0 = slow: for small-sized volumes;
•
1 = medium: for medium-sized volumes;
•
2 = fast: for large-sized volumes;
•
3 = custom.
The
“custom”
value contains special gains that can be set on request by Camozzi technicians, for
this reason, the selection of this value is usually not allowed.
13.2.12.
Pressure regulation check
Enables to check the regulated pressure, can either be 0 = Disable or 1 = Enable.
13.2.13.
Pressure regulation timeout
Sets the time to achieve the regulated pressure, its value is expressed in milliseconds from 0 to
60000 (1 minute).
13.2.14.
Charge coil health status
Indicates the health status as a percentage of the charge coil, is either visible or not according
to the diagnostics level of the Regulator.
13.2.15.
Discharge coil health status
Indicates the health status as a percentage of the exhaust coil, is either visible or not according
to the diagnostics level of the Regulator.
13.2.16.
Charge coil commands number
Indicates the number of commands of the charge coil, is either visible or not according to the
diagnostics level of the Regulator.
13.2.17.
Discharge coil commands number
Indicates the number of commands of the exhaust coil, is either visible or not according to the
diagnostics level of the Regulator.
13.2.18.
Charge coil maximum activation time
Indicates the total work time of the charge coil expressed in ms, is either visible or not according
to the diagnostics level of the Regulator.