![Camille Bauer SIRAX MT7000 Operating Manual Download Page 28](http://html1.mh-extra.com/html/camille-bauer/sirax-mt7000/sirax-mt7000_operating-manual_3673833028.webp)
PM 1001939 000 00
AC/DC Current and Voltage Converter SIRAX MT7000/MT7050
28/32
40016
Sec. for max RMS
Seconds 1..30 for MAX RMS value. If the register is 0,
then the absolute MAX RMS is given
Unsigned short
R/W
0
40017
Sec. for min RMS
Seconds 1..30 for min RMS value. If the register is 0,
then the absolute min RMS is given
Unsigned short
R/W
0
40018
Sec. for mean DC
Register in seconds (0..30) for DC average
Unsigned short
R/W
0
40019
Sec. for max DC
Seconds 1..30 for MAX DC value. If the register is 0,
then the absolute MAX DC is given
Unsigned short
R/W
0
40020
Sec. for min DC
Seconds 1..30 for min DC value. If the register is 0,
then the absolute min DC is given
Unsigned short
R/W
0
40021
Sec. for mean AC
Register in seconds (0..30) for AC average
Unsigned short
R/W
0
40022
Sec. for max AC
Seconds 1..30 for MAX AC value. If the register is 0,
then the absolute MAX AC is given
Unsigned short
R/W
0
40023
Sec. for min AC
Seconds 1..30 for min AC value. If the register is 0,
then the absolute min AC is given
Unsigned short
R/W
0
40024
Alarm Register Start
Address
Float value Starting address for alarm (40149 I RMS,
40151 I DC, 40153 I AC, ecc)
Unsigned short
R/W
40149
40025
I Start
Current (in A)/temperature (in °C) (see Flag Measure-
ment) which corresponds to Out start
Float (LSW first)
R/W
0
40027
Out Start
Output value (in mV o in uA) of the chosen output
corresponding to I start
Unsigned short
R/W
4000
40029
I Stop
Current (in A)/temperature (in °C) (see Flag Measure-
ment) which corresponds to Out stop
Float (LSW first)
R/W
5
40031
Out Stop
Output value (in mV o in
μ
A) of the chosen output
corresponding to I stop
Unsigned short
R/W
20000
40033
Steinhart Hart A
Coeff Steinhart-Hart A
Float (LSW first)
R/W
0
40035
Steinhart Hart B
Coeff Steinhart-Hart B
Float (LSW first)
R/W
0
40037
Steinhart Hart C
Coeff Steinhart-Hart C
Float (LSW first)
R/W
0
40039
Alarm Trip Value
Alarm Threshold
Float (LSW first)
R/W
0
40041
Alarm Hysteresis
Alarm Hysteresis
Float (LSW first)
R/W
1
40147
Status
Bit 0: flash settings error
Bit 1: flash calibration error
Bit 2: Current Over Range; Bit 3: Current Under Range
Bit 4: don’t care
Bit 5: RTD Open or broken
Bit 6: Current Zero crossing detecting
Bit 7: Switch open
Bit 8: RTD third wire error (Resistance > 20 Ω)
Bit 9: RTD out of the range (-200...+600°C)
Bit 10: Ah storing error
Bit 11: Analog Output over range
Bit 12: don’t care
Bit 13: Alarm detection
Bit 14: Analog Output under range
Bit 15: don’t care
Unsigned short
R
0
40148
V I Out
Voltage or current output (in mV or mA)
signed short
R
40149
I RMS
RMS value (A)
Float (LSW first)
R
10151
I DC
DC value (A)
Float (LSW first)
R
40153
I AC
AC value (A)
Float (LSW first)
R
40155
Frequency
Frequency (Hz)
Float (LSW first)
R
40157
Crest Factor
Crest Factor
Float (LSW first)
R
40159
THD
Total Harmonic Distortion
Float (LSW first)
R
40161
I 0 RMS
DC Harmonische
Float (LSW first)
R
40163
I 1 RMS
1. Harmonic
Float (LSW first)
R
40165
I 2 RMS
2. Harmonic
Float (LSW first)
R
40167
I 3 RMS
3. Harmonic
Float (LSW first)
R