background image

15

16

TB

9

TB

8

TB

7

TB6

TB

5

Resistor may

be included in 

readout device. 

*

PO

W

ER

+

7
8
9

10
11
12

GROUND

SCREW INSIDE 

ENCLOSURE

ANALOG READOUT

POWER SUPPLY

8-30 VDC

GND

ANALOG OUTPUT (TB4)

WITH POWER SUPPLIED VIA MAIN BOARD (TB2)

SCANNER 2000 

Main Circuit Board

PN: 9A-30160010

Expansion

Board PN:

9A-30160014

TB2

TB4

Analog Output 

(4-20 mA)

 

The 4-20 mA linear  

current output can be 

configured with  

ModWorX™ Pro  

software to represent 

any parameter in the 

holding registers. This 

output requires a two-

conductor cable to be 

connected to an 8 to 30 

VDC power supply (volt-

age required is depen-

dent on loop resistance) 

and an analog readout 

device to be located in 

the remote location.  

 

The graph above shows 

the minimum voltage 

For example, if a power 

supply voltage of 24 

volts is available to 

power the current loop, 

the maximum load 

resistance would be 800 

ohms.

800

200

0

8

12

24

30

OPERATING

REGION

LOOP SUPPLY VOLTAGE (VDC)

LO

AD RESIST

ANCE (

OHMS)

required to power the 

instrument for a given 

loop resistance. In addi-

tion, the mathematical 

relationship between 

loop voltage and load 

resistance is given.  

Summary of Contents for Scanner 2000 Expansion Board

Page 1: ... from the main board if necessary to guide the expansion board into position Remove the standoff from packaging and press it into the hole near the center of the main board until it snaps into place Guide the expansion board over the stand off and align the pins on the under side with the headers on the main board 1 2 When the board is positioned correctly text on both boards should face the same ...

Page 2: ...de pulse frequency signals which includes signals from a turbine meter equipped with a preamplifier or signals from a PD meter via contact closure The Scanner 2000 can calculate flow from no more than two pulse frequency inputs at a time Therefore a pulse input can be used simultaneously with only one turbine input main board or expansion board PULSE INPUT TB8 25 26 TB9 TB8 TB7 TB6 TB4 TB5 PULSE I...

Page 3: ...5 V 0 5 V or 4 20 mA signal can receive read ings from a pressure or temperature sensor for use in AGA 7 gas cal culations Alternatively they can be used to log measurements from any device with a 1 5 V 0 5 V or 4 20 mA output Transmitter power is provided by the Scanner only when the Scanner is externally powered The output voltage equals the input voltage less 0 25 VDC and is limited to 20 mA If...

Page 4: ... holding registers This output requires a two conductor cable to be connected to an 8 to 30 VDC power supply volt age required is depen dent on loop resistance and an analog readout device to be located in the remote location The graph above shows the minimum voltage For example if a power supply voltage of 24 volts is available to power the current loop the maximum load resistance would be 800 oh...

Reviews: