ANALOG READOUT
POWER SUPPLY
8-30 VDC
GND
ANALOG OUTPUT (TB4)
WITH POWER SUPPLIED VIA MAIN BOARD (TB2)
SCANNER 2000
Main Circuit Board
PN: 9A-30160010
Expansion
Board PN:
9A-30160014
TB2
TB4
Analog Output
(4-20 mA)
The 4-20 mA linear
current output can be
configured with
ModWorX™ Pro
software to represent
any parameter in the
holding registers. This
output requires a two-
conductor cable to be
connected to an 8 to 30
VDC power supply (volt-
age required is depen-
dent on loop resistance)
and an analog readout
device to be located in
the remote location.
The graph above shows
the minimum voltage
For example, if a power
supply voltage of 24
volts is available to
power the current loop,
the maximum load
resistance would be 800
ohms.
800
200
0
8
12
24
30
OPERATING
REGION
LOOP SUPPLY VOLTAGE (VDC)
LO
AD RESIST
ANCE (
OHMS)
required to power the
instrument for a given
loop resistance. In addi-
tion, the mathematical
relationship between
loop voltage and load
resistance is given.