background image

2

Relay response to malfunctions (see chapter 6 Troubleshooting):

The relay picks up when the
loop is activated and drops
out when the loop is exited.

Loop

Relay

On delay:
The relay picks up after the
time t when the loop is acti-
vated and drops out when
the loop is exited.

Loop

Relay

tt

Off delay:
The relay picks up when the
loop is activated and drops
out after the time t when the
loop is exited.

Loop

Relay

tt

Activation pulse:
The relay picks up when the
loop is activated and drops
out again after the time t.

Loop

Relay

tt

Impulse by leaving the loop:
By leaving the loop,
the relay picks up after
the time t, relay drops out.

Loop
Relay

tt

Max. presence:
he relay picks up when the
loop is activated and drops
out again after leaving, but
at least after the time t.

Loop

Relay

tt

1.Door/gate 

systems

A malfunction causes
the output relay to be
released. The alarm
relay drops out.

2. Barrier

A malfunction causes
the output relay to pick
up. The alarm relay
drops out.

3. Quiescent

current

A malfunction causes
the output relay to be 
released. The alarm
relay drops out.

4. Direction logic

(2-loop device
only)

A malfunction causes
the output relays to be
released. The alarm
relay drops out.

*factory settings

Note: The set parameter values are retained after a power failure, independent from the “Protection against power failure” function.

P  1

=  Protection against power failure activated: The sensitivity is restricted to 1–5.

Time functions

, time unit

2  

and time factor 

(Einstellungen siehe Tabelle 4.11a)

4.3

Parameters
1: Door and gate 

The assigned output relay picks up when the loop is activated and drops out when the loop returns to a non-activated condition.

2: Barrier

The assigned output relay picks up when the loop is activated and drops out when the loop returns to a non-activated condition.

3: Quiescent current 

The assigned output relay drops out when the loop is activated and picks up again when the loop returns to a non-activated condition.

4: Direction logic 

Output 1 switches if an object moves from loop 1 to 2. Output 2 switches if an object moves from loop 2 to 1. 

Both loops

must be

activated for a short time. The outputs are reset again when loop 2 returns to a non-activated condition. Both loops must have re-
turned to a non-activated condition for another direction detection.

0: Loop 2 

Loop 2 can be deactivated in a 2-loop device.

Basic functions 

(see Table 4.11a for settings)

4.2

Signal characteristics with protection against power failure active (Function 9 = 1)

4           .9.1

For Activation (e.g. Barriers)

Basic function 0 = 

2 Barrier systems

Without power

Initialisation

Free

Occupied

Free

For Safeguarding (e.g. Barriers, bollards)

Basic function 0 = 

3 Quiescent current

Without power

Initialisation

Free

Occupied

Free

Output

Output

The sensitivity  

(=Sensitivity) of the loop detector can be adapted in 9 stages: 

51 = 

Lowest sensitivity, 

59 = 

Highest sensitivity, 

54 = 

Factory setting. 

In a device with 2 outputs, output 2 can be either activated or deactivated. 

Four different frequencies F1, F2, F3, F4* can be set in order to avoid interference when using several loop detectors.

The direction logic function can only be used with a 2-loop device. Direction logic must have been set in the basic function (see chapter 4.2). Detection
can be performed from: 

Loop 1 to loop 2 

From loop 2 to loop 1 

from both directions

ASB (=

A

utomatic 

S

ensitivity 

B

oost). ASB is required in order to be able to recognise trailer drawbars after activation.

Sensitivity 4 (see Table 4.11a for settings)

4.4

Automatic Sensitivity Boost ASB 

(see Table 4.11a for settings)

4.5

Frequency

(see Table 4.11a for settings)

4.6

Direction logic

(see Table 4.11a for settings)

4.7

Output 2

(see Table 4.11b for settings)

4.8

Protection against power failure 

9  

(see Table 4.11a for settings)

4.9

Display after start-up:

1

Touch the «Mode» button once
to change to configuration
mode

Mode
Sim1

1

Display after start-up:

1

2

Touch the «Mode» button once
to change to configuration
mode

Mode
Sim1

1

Mode
Sim1

2

 

Loop 2 is 
selected

 

Loop 1 is 
selected

1- loop device

2- loop device

Changeover from operation to configuration mode

4.10

common
nc

no

common
nc

no

common
nc

no

common
nc

no

Reviews: