Press button P
J
to confirm the
minimum ON time and switch to
adjusting the proportional band.
Use the
buttons to adjust the
value of the proportional band to
between 1 and 3 °C.
The graph and table
K
can help you decide on the type of program or value of the
parameter to be added.
Press button P to exit programming.
N.B. All parameters related to the configuration of the type of temperature management
algorithm are saved in the permanent memory of the device.
Temper
atur
e
Time
Setpoint
Prog. Cycle length
(minutes)
Minimum ON
time (minutes)
Proportional
band
Type of system
P1
10
1
1.5 °C
Base for gas burner, fan coils, zone
valves, aluminium radiators
P2
5
1
1.5 °C
Electric radiators
P3
20
2
1.5 °C
Radiant or underfloor systems, cooling
P4
from 5 to 40 from 1 to 5
from 1 °C to 3 °C
Summary of Contents for BPT TH/350