background image

Page 2 of 11

WC13PS SERIES RESTROOM CONTROL

INSTALLATION INSTRUCTIONS

Selecting a Mode

The CX-WC13PS has two Restroom applications built in (Mode 
7 & 8). The default mode for the CX-WC13PS is Mode 7 
(normally unlocked).

Determining which mode is correct for you will be based on 
whether the Restroom will be normally unlocked (Mode 7) or 
normally locked (Mode 8). 

There are three LED displays that will allow you to see what mode 
you have selected when advancing through the modes. To change 
the mode of the CX-WC13PS simply press the MENU button once 
and use the UP button to advance to the desired mode.

Editing the Settings for a Mode 

Camden builds in typical times for lock release and door 
operator activation and is ready to use without changing any 
parameters. If you need to change the timing or delay for an 
output, it can be done by pressing the “MENU” button within the 
mode you selected. Once the option is selected you can use the 
“UP or DOWN” buttons to select the timing needed.

The first option (H & 1 flashing) will be how long relay 1 will be 
activated for (0-50 seconds). The second option (d & 1 flashing) 
will be how long to wait before activating relay 2 (0-15 seconds). 
The third option (H & 2 flashing) will be how long relay 2 will be 
activated for (0-50 seconds). The fourth option (d & 2 flashing) 
will be how long to wait before activating relay 3 (0-15 seconds). 
The fifth option (H & 3 flashing) will be how long relay 3 will be 
activated for (0-50 seconds). See chart below.

Factory Reset (Defaulting the CX-33)

To return the CX-33 back to its factory default settings you will 
need to remove power, then hold down the “MENU” button 
while powering up the CX-33. Once started you will see the 
firmware version listed then a number “1” will be displayed. 
Reconnect your power and press the “MENU” button once then 
use the “UP” or “DOWN” button to advance to the desired mode. 

Fully test the operation of the CX-WC13PS for proper functionality.

Display (M)

Description ( Mode you are in)

Parameters (1-15 )

H, then 1

Relay 1 Hold Time

0.0 to 50 seconds

d, then 1

Relay 2 Delay Time

0.0 to 15 seconds

H, then 1

Relay 2 Hold Time

0.0 to 50 seconds

d, then 1

Relay 3 Delay Time

Depends on Mode

H, then 1

Relay 3 Hold Time

0.0 to 50 seconds

d

Sets the display ON or OFF during operating mode

ON or OFF

A

Input delay on Activate. If other than 0.0 is selected, the input must 

be held in for the time period chosen before the CX-33 will activate.

0.0 to 10 seconds

1

Set Dry Input 1 to activate on normally open or normally closed contact.

N/O OR N/C

2

Set Dry Input 2 to activate on normally open or normally closed contact.

N/O OR N/C

3

Set Dry Input 3 to activate on normally open or normally closed contact.

N/O OR N/C

4

Set Dry Input 4 to activate on normally open or normally closed contact.

N/O OR N/C

5

Set Dry Input 5 to activate on normally open or normally closed contact.

N/O OR N/C

Summary of Contents for CX-WC13AXFM-PS

Page 1: ...the PBTN input on its Aura board causing its N O relay contact to send a momentary closure to inside PUSH TO LOCK causing the CX WC13PS to lock the Restroom and switch the Aura colors from green to re...

Page 2: ...ctivating relay 3 0 15 seconds The fifth option H 3 flashing will be how long relay 3 will be activated for 0 50 seconds See chart below Factory Reset Defaulting the CX 33 To return the CX 33 back to...

Page 3: ...t and the surface aura enclosure align FOR CM 45 454SE1 CM 45 854SE1 CM 45 4 SWITCHES a Use the 6 32 hex head screws to tighten the aura insert slightly b Fit in the assembled CM 45 4 by locating the...

Page 4: ...screws to completely tighten in place 4 Place the aura board inside the flush aura enclosure making sure the screw holes on the aura board align with the screw holes inside the Flush aura enclosure Us...

Page 5: ...screws and lockwashers 6 Secure M5x12 screws holding mounting brackets to jamb 4 Installation Mounting Bracket Spacer Spacer Option Spacer M5x12 Flat Head Screw 2pcs Jamp M5x12 Screw Vertical Centerli...

Page 6: ...een input wires Fail Safe Changing Fail Secure 24VDC Red 24V Black Blue Green Ground How to modify fail safe to fail secure or vice versa 1 Loosen the screw as per the product diagram below 2 Rotate t...

Page 7: ...ITTEN PERMISSION OF CAMDEN DOOR CONTROLS IS PROHIBITED Light ring on switch will turn red when door is locked to unlock door and exit TO LOCK THIS DOOR WAIT FOR DOOR TO CLOSE 40 81C021 Place sign on t...

Page 8: ...lack Vinyl English Label DOOR LOCKED WHEN RED UNLOCKED WHEN GREEN OCCUPIED WHEN RED VACANT WHEN GREEN 9 CM SFF1 Black Vinyl French Label OCCUP LIBRE PORTE BARR E PORTE D BARR E 10 CM SFFE1 Black Vinyl...

Page 9: ...WC13PS SERIES RESTROOM CONTROL INSTALLATION INSTRUCTIONS Page 9 of 11 File WC13PS Restroom Controls Manual indd Rev February 26 2020 Part No 40 82B238 Questions Call us toll free at 1 877 226 3369 or...

Page 10: ...gration Model 60 40E033 CM 2520 4855SE1 or similar PUSH TO OPEN PUSH TO LOCK Inside Push To Open always unlocks opens door Push to Lock combination Switch 12 24 Power Remote N O Relay Output Push To O...

Page 11: ...Page 11 of 11 WC13PS SERIES RESTROOM CONTROL INS TA LLATIO N INS TR UCTIO NS CABINET BASE L C L C 7 7 8 200 2 mm Cabinet Base Mounting Template 6 152 7 mm 6 152 7 mm 9 5 8 243 9 mm 11 1 16 281 4 mm...

Reviews: