CX-DE1200 Delayed Egress Electro Magnetic Lock

INSTALLATION INSTRUCTIONS

4. FEATURES

• Holding Force up to 1200 Lbs. (Not validated by UL)
• Field selectable exit delay time 15 or 30 seconds
• Nuisance Delay period either 1, 2 or 3 seconds
• 75dB Buzzing Tone with LED segment bar display time 

seconds & field selectable voice alerts

• Choice of sensor to be activated: 

- Door Motion 

- Door Exit Device with momentary normally open contact 

- Push Bar with momentary normally open contact

• Auto Start Up: 

- Occurs when power supply is restored and/or the fire panel is   

  restored (When allowed by Building & Fire Life Safety Code)

• Manual Start Up: 

- This is a California & UBC Building Code Compliant Feature. 

Only after power supply restoration and fire panel reset 

may the lock be Reset manual at the opening. This lock can 

be reset with the built-in reset key switch or an external key 

switch or a reset switch connected to the door

• Vandal resistant Proximity Trigger Sensor
• Auto Sensing Voltage Power Input 12/24 VDC
• Reverse power protection: 

If someone hooks power up backwards, the board simply 

does not turn on, protecting it from damage

• Optional Connection for Auxiliary Lock, CX-DE1201 (Double 

Leaf Door)

• Hall Effect Sensor Monitoring Output
• Tamper Switch Output
• Tailgating Prevention - door will re-lock as soon as it closes
• Anti-Pass Back / Auto re-lock: 

If door doesn't open after the count down, the door will 

automatically re-lock.

5. INSTALLATION CONCEPT AND ACCESSORIES

Seven configuration versions are available to be compliant to regional jurisdictions.

Models

Delay Release Time 

(Seconds)

Nuisance Delay 

(Seconds)

Reset After Alarm

Lock Status on Power-Up

Fixed

Selectable

Fixed

Selectable

Selectable

Fixed

Fixed

Selectable

CX-DE1200

15 or 30

1 or 2

Manual

Locked / Unlocked

CX-DE1200-N2

15

0 or 1

Manual

Locked / Unlocked

CX-DE1200-N3

30

0 or 1

Manual

Locked / Unlocked

CX-DE1200-N4

15

0 or 1

Manual Unlocked

CX-DE1200-B1

15

0 or 3

Auto / Manual

Locked / Unlocked

CX-DE1200-B2

30

0 or 3

Auto / Manual

Locked / Unlocked

CX-DE1200-B3

15

0

Auto / Manual

Locked / Unlocked

N# = NFPA Compliance     

  

     B# = BOCA Compliance

BOCA Compliance

Manual Reset:

 Is achieved by authorized personnel closing the door after an alarm and actuating the integral reset key switch 

      

             or by momentarily closing a contact connected to the remote RESET terminal.

Automatic Reset:

 Reset will automatically be initiated once the door has been opened, then closed and remains closed for 

                                   30 consecutive seconds.

Release Time

Warning Type

WARNING!

Contact authority having jurisdiction for approval prior to 

selecting release time, nuisance time and start-up settings.

!

Languages

Voice Type

Nuisance Time

R-Exit Time

Trigger type
Start-Up State
Door POS Alarm
Anti Pass Back

Dip Switch Settings

Summary of Contents for CX-DE1200

Page 1: ...Output 12 24 VDC 1A Lock Status Relay Rating Max 30 VDC 2A 1 pF Alarm Output Rating Max 30 VDC 2A 1 pF DPS Rating Max 30 VDC 0 1A 1 pF BondSensorRatingMax 30 VDC 2A 1 pF ATS Rating Max 30 VAC 42 4 VDC 5A 1 pF Operating Temperature 0 55 C 32 131 F Operating Humidity 0 95 non condensing Dimensions Lock 11 H x 3 W x 3 D 280mm x 76mm x 74 5mm Dimensions Armature Plate 11 H x 2 5 8 W x 1 D 280mm x 68mm...

Page 2: ... Prevention door will re lock as soon as it closes Anti Pass Back Auto re lock If door doesn t open after the count down the door will automatically re lock 5 INSTALLATION CONCEPT AND ACCESSORIES Seven configuration versions are available to be compliant to regional jurisdictions Models Delay Release Time Seconds Nuisance Delay Seconds Reset After Alarm Lock Status on Power Up Fixed Selectable Fix...

Page 3: ...led Factory default setting Jumper J10 Fire Panel Input Uninstalled Only if a dry contact NC from a fire alarm panel or smoke detector system is connected to the Fire P terminals Door unlocked alarm sounding until reset Display Mode Jumper Settings Push Bar Optional CM 120i Keypad optional AC Main Fire Panel 2 Core Cable 3 Core Cable Power Supply Push Bar Ex Trig Keypad Key Switch Built In Key Swi...

Page 4: ... hole position IG DE1200 280 Ver 1019 Out Swing Door Only Door Frame Door Frame Door Frame Door Frame Armature Plate Armature Housing Temporary mount with self tapping screw EZ Interlocking Mounting Plate Screw 2 Screw 1 2 Drill mark the screw hole according to the template holes Door Frame Mounting Template Door 1 Door Door Door Spring Armature Screw Proxy Trigger Door Step 1 Close the door posit...

Page 5: ...g screws Step 6 Align the lock unit with the mounting plate Fix the lock unit to the mounting plate with the allen key given through fixing the screw Carefully screw into the mounting plate to avoid stripping the threads Check and confirm the alignment and mating surface between the armature plate and lock unit NOTICE Loosen screw 1 or 2 to re align the mounting plate and position the lock unit ma...

Page 6: ...OTICE Standard operation of the lock depends on the proxy sensor being able to detect the proxy trigger when the door is swing closed A minor adjustment can be made to the proxy sensor height for fine tuning Step 11 Fine Tuning Proxy Sensor Height Turning proxy sensor holder clockwise CW will increase the height of the proxy sensor from the front cover surface hence decreasing the gap between the ...

Page 7: ...counted along with verbal exit guidance When the LED bar display reaches zero the lock will release The verbal voice guidance changes to a continuous verbal instruction announcing Door Unlocked In TONE ONLY mode the countdown will be accompanied with a beeping tone only and a continuous tone is heard once the Release time cycle ends Languages The voice message can be in 3 languages which are field...

Page 8: ... Internal OFF Unlocked Not Used Stand by OFF 5 OFF Fixed Manual 15 1 ON 15 Sec OFF OFF External ON Unlocked Alarm ON 1 ON NFPA OSHPD Compliant Power Up unlocked and manual reset is fixed 20 Sec ON OFF 30 Sec OFF ON Not Used Switch 8 B1 15 Not Used 0 OFF 1 Sec ON ON Internal OFF Unlocked OFF Stand by OFF Manual OFF 15 3 ON 15 Sec OFF OFF External ON Locked ON Alarm ON Auto ON BOCA Compliant Automat...

Page 9: ...is NOT on the armature Anti Tamper Switch This contact will change state when the cover is removed External Trigger Wire from of Tandem CX DE1220 lock Power Supply for accessories Fire Alarm Input Supervised Normally Closed J10 jumper must be removed Wire connection to Tandum Lock CX DE1220 Lock Status The bond sensor will monitor the surface of the armature This contact will change state when the...