Delayed Egress Lock Maintenance Manual
INSTALLATION INSTRUCTIONS
File: Delayed_Egress_Maintenance_
Manual.indd
Revision: Sept 27th 2021
Part No.: 40-82B292
TROUBLESHOOTING
Problem
Solution
Lock has no holding force
Check the power supply. Voltage should be 12 to 24 VDC +/- 10%.
Check wiring of power supply and releasing devices.
Lock will hold a screwdriver or set of metal pliers,
but the door will not lock.
Check to ensure the armature plate is correctly aligned to the maglock. Follow the armature
plate mounting instructions on the template and the installation manual 40- 82B236
Lock is operating and locking but it hums against
the armature plate.
Check that the power supply is filtered DC. The humming is caused by AC on the DC supply.
A proper filtered and regulated DC power supply will resolve the issue.
There is a latency of the lock not releasing after
power is removed.
Refer to Figure A and check the placement of any suppression devices. Residual magnetism
is related to the presence of electricity (i.e., capacitance) in the lock circuit. Degaussing or
dimpling the lock are not advised since it will cause unintended consequences.
MAINTENANCE SCHEDULE
Company Name:
_________________________________________________________
DC Power Supply
(filtered & regulated)
Switch
Maglock
+
‐
DC Power Supply
(filtered & regulated)
Switch
Maglock
+
‐
Recommended
placement of switch to
ensure instant release.
Placing the RTE switch
(push plate or PIR) on the
wrong leg may cause the
bond to collapse more
slowly than expected.
Ensure the switch
interrupts the positive
wire and not the negative
wire.
Maglock
+
‐
MOV
Maglock
+
‐
Never connect a
parallel reverse diode
as shown.