CM-9800 TOUCH BUTTON SWITCH
INSTALLATION INSTRUCTIONS
DIP SWITCH SETTINGS
1 – Relay Time (0.5 to 60 seconds or toggle mode)
2 – not used
3 – Buzzer ON/OFF
4 - Backlight ON/OFF
5 - LED Control
6 – Default state – State of the controller's input for the LEDs
SET RELAY TIMER – DIP SWITCH 1
CM-9800 operates in Toggle or Pulse mode. The time is set by
Dipswitch 1 Setting
.
Put the Switch 1 in position ON. The unit will start emitting
beeps. Count the beeps and then stop them by positioning the
Switch 1 to OFF. The number of beeps defines the relays time,
according to the table below (2 beeps - 0.5 sec, 3 beeps - 1 sec...).
Switch 1
Number of Beeps
Time
ON
1 beep
Toggle Mode
(ON/OFF Mode)
ON
2 beeps
0.5 Seconds
ON
3 beeps
1 Seconds
ON
4 beeps
2 Seconds
ON
5 beeps
5 Seconds
ON
6 beeps
10 Seconds
ON
7 beeps
15 Seconds
ON
8 beeps
30 Seconds
ON
9 beeps
45 Seconds
ON
10 beeps
60 Seconds
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
DIP SWITCH 1 RELAY TIME
BUZZER, BACKLIGHT AND LED CONTROL
Position 3, 4, 5, and 6 On Dip Switch
Example of externally controlled LED light, where the exit
button's light follows the reader's light.
ON
1 2 3 4 5 6
LR-
LED Red
LED Green
LED COM
LG-
LED Red
LED Green
LED com (Ground)
Access Control Panel