ULP
User manual
MODBUS Sensor Data Requests
Measurements all have a resolution of 0.1 but are reported as 10*.
8.2 m/s is returned as a value 82. The user must /10 in order to reinsert the
decimal precision.
Address
Register
Access
Type
Response
Range
Data
Type
Description
200
201
Read
0 to 15†
16-bit
Signed
Int
System
Status†
201
202
Read
0 to 500*
16-bit
Signed
Int
Wind speed
(m/s) (3
second
moving
average)
202
203
Read
0 to 3599*
16-bit
Signed
Int
Wind
direction (°)
(3 second
moving
average)
203
204
Read
0 to 500*
16-bit
Signed
Int
2 min avg
wind speed
204
205
Read
0 to 3599*
16-bit
Signed
Int
2 min avg
wind
direction
205
206
Read
0 to 500*
16-bit
Signed
Int
10 min avg
wind speed
206
207
Read
0 to 3599*
16-bit
Signed
Int
10 min avg
wind
direction
207
208
Read
0 to 500*
16-bit
Signed
Int
Wind gust
speed
208
209
Read
0 to 3599*
16-bit
Signed
Int
Wind gust
direction
210
211
Read
0 to 500*
16-bit
Signed
Int
5 min avg
wind speed
211
212
Read
0 to 3599*
16-bit
Signed
Int
5 min avg
wind
direction
212
213
Read
0 to 500*
16-bit
Signed
Int
5 min Wind
gust speed
213
214
Read
0 to 3599*
16-bit
Signed
Int
5 min Wind
gust
direction
† If not applicable to ULP-M, the register should report a value of zero (0).
* See Data Format section for numeric conversions.