LAMP
ACTION
UNIT DOES NOT OPERATE
MAINS
RED
ON
FAULT
AMBER
ON
FRIDGE FAULT
1 AND/OR 2
AMBER
1/2
OFF
Check thermal motor starters for fans have not tripped. Check soft start has not
tripped (if fitted). Check external flow switch is made (if fitted).
DEFROST
WHITE
OFF
WATERFLOW
GREEN
ON
FAN ON COMPRESSOR OFF
MAINS
RED
ON
FAULT
AMBER
OFF
Unit on normal defrost. If after 20 minutes the defrost lamp is still on, check that the
air temperature is not below 10°C for M models or -15°C for MY models.
FRIDGE FAULT
1 AND/OR 2
AMBER
1/2
OFF
DEFROST
WHITE
ON
Check 12 hours have elapsed since first power up.
WATERFLOW
GREEN
ON
UNIT OPERATES INTERMITTENTLY
MAINS
RED
ON
FAULT
AMBER
ON/OFF
FRIDGE FAULT
1 AND/OR 2
AMBER
1/2
OFF
Check water flows are not restricted and that the electrical supply is adequate.
Check that linked in external equipment is not the cause of the fault.
DEFROST
WHITE
OFF
WATERFLOW
GREEN
ON/OFF
If the machine suffers from poor performance and the low pressure
switch(es) trip and cannot be reset (the fridge fault lights also
illuminate) then this may be a symptom of a refrigerant leak.
Put the unit is Standby mode and isolate from the power supply.
Contact a refrigerant technician authorised in accordance with EU
517/2014 as soon as possible.
32
SD566252 ISSUE 51
PR0-PAC SYSTEM OWNER INSTALLATION MANUAL