background image

C-PAC+ swimming pool heat pumps 
CPT 6, 8, 12, 15, 20

Owner Installation Manual 1006905 Issue 2

Summary of Contents for C-PAC+ CPT12 ALY

Page 1: ...C PAC swimming pool heat pumps CPT 6 8 12 15 20 Owner Installation Manual 1006905 Issue 2...

Page 2: ...s This appliance can be used by children from 8 years and above and persons with reduced physical sensory or mental capabilities or lack of experience and knowledge if they have been given supervision...

Page 3: ...N IN SWIMMING POOLS 16 3 7 ELECTRIC WIRING AND SUPPLY 16 3 8 CONNECTING THE HEAT PUMP TO THE POWER SUPPLY 17 3 9 POOL PUMP SYNCHRONISATION TERMINALS P1 AND P2 18 3 10 REMOTE ON OFF CONNECTION 19 4 0 U...

Page 4: ...and follow all safety advice The refrigerant used in this heat pump is R32 This refrigerant is environmentally friendly but safety instructions must be strictly adhered to The refrigerant used in the...

Page 5: ...e following location requirements must be fulfilled The heat pump must be kept away from sources of fire or naked flames The heat pump must be installed operated and stored where the floor area is lar...

Page 6: ...up without warning Electric storms can damage electronic equipment Ideally the heat pump should be switched off at the mains HEAT PUMP MALFUNCTION WARNING Isolate heat pump electrically and wait 3 min...

Page 7: ...nts may not contain an odour Appliance shall be installed operated and stored in a room with a floor area larger than Xm2 where X is the minimum area shown in section 3 2 and section 8 0 The heat pump...

Page 8: ...eat pump by the water inlet or outlet connections If this is done the titanium heat exchanger inside the heat pump could be damaged 2 2 ACCESSORIES These accessories are provided with the heat pump 2...

Page 9: ...at exchanger High pressure and low pressure protection Soft start and wide voltage application Multi function operation Can also be used for cool pools 2 4 OPERATING CONDITIONS AND RANGE Air temperatu...

Page 10: ...absorbs energy from the air drawn through it To function effectively the heat pump must have access to the fresh air it needs Air must not recirculate The air leaving the heat pump must not be sucked...

Page 11: ...rea or where required to pass air through a wall etc Ensure the heat pump is sealed against the wall so the outlet air cannot recirculate Ensure the hole through the wall is sealed to avoid the outlet...

Page 12: ...WNER INSTALLATION MANUAL 350 cm Swimming pool or spa To comply with safety regulations regarding electrical installations in wet areas the heat pump must be installed at least 350cm away from the edge...

Page 13: ...evel in a room stays below their lower flammability limit LFL European standard EN378 defines requirements to remain far below the lower flammable limit in case of accidental leakage By choosing the l...

Page 14: ...tiser fitted Non return valve Sanitiser or chemical dosing device If fitted Aux heater If fitted Filter Pump To waste for winterising drain down 100mm Condensate water to waste Spare port for winteris...

Page 15: ...must be supported to avoid excessive strain on the connections 4 Water quality must be maintained See warranty conditions 3 5 INITIAL CHECKS Start the filtration pump before the heat pump is turned o...

Page 16: ...lectrical items such as metal filters pump strainer boxes heat exchangers steps and handrails It is highly recommended that bonding be retrofitted to existing pools which may not be protected by this...

Page 17: ...within 2m and in line of sight of the heat pump Secure cables using cable clamps and feed through cable entry points in machine Isolator which disconnects all poles fitted within 2m and in line of si...

Page 18: ...s If the pool does not need heating cooling the filter pump will be turned off after 5 minutes until the next sampling period or the next timeclock pump on period If the pool needs heating cooling the...

Page 19: ...itch which are marked Remote on off and are situated below the mains in terminals The heat pump is supplied with a link wire in the remote terminals for use without a switch When fitting a remote swit...

Page 20: ...mode Auto mode Fan running Heating mode 88 88 88 88 Current water inlet temperature SET IN Ambient temperature ROOM OUT Error codes show here Timer function enabled Timer function disabled Fault indi...

Page 21: ...eat pump is defrosting the symbol will appear It will disappear when defrost is complete e Clock setting Press the to enter the timer settings The icon will flash Press M to set hour with p and q Pres...

Page 22: ...eating Set temperature too low Set desired heating temperature 3 minutes start delay Wait for the delay timer to time out Inaccurate switch action Stop the machine and cut off the power supply immedia...

Page 23: ...time when in standby to prevent frost build up This does not replace winterisation Heat pump will resume standby one process is completed 5 3 FAULT CODES No Display Description of fault code 1 P1 Eva...

Page 24: ...Check bolts cables and connections regularly Repair service and disposal of redundant heat pumps must be completed by authorised technicians It is illegal to allow refrigerant gases to escape to air D...

Page 25: ...67 4 6 Rated input current A 5 49 6 26 9 42 12 1 12 3 Maximum input current A 10 0 15 3 18 3 25 3 11 1 Rated RCD A 30mA 30mA 30mA 30mA 30mA Rated fuse aM MCB type C A 20 20 32 40 20 Sound pressure le...

Page 26: ...on F H Pressure gauge J G Air inlet Air inlet D A B C Water Inlet A B C D E F G H J CPT6 ALY 381 620 363 405 968 370 96 654 741 CPT8 ALY 381 620 363 405 968 370 96 654 741 CPT12 ALY 466 750 443 490 11...

Page 27: ...R CPT6 ALY 470 470 327 342 493 560 50 CPT8 ALY 470 470 327 342 493 560 50 CPT12 ALY 545 545 350 389 598 608 50 CPT15 ALY 545 545 350 389 598 608 50 CPT20 BLY 650 650 400 446 713 709 50 M N Water Inle...

Page 28: ...ive To provide frost protection To eliminate corrosion problems To inhibit electrical components 1 Switch off electrical supply to heat pump 2 Remove external fuses and keep in safe place away from he...

Page 29: ...icient or in any way incorrect 8 The fan amps and duct pressure are outside the specified limits 9 The air flow to and from the machine is outside the specified limits If in doubt or if advice is requ...

Page 30: ...30 1006905 ISSUE 2 OWNER INSTALLATION MANUAL 12 0 DECLARATION OF CONFORMITY...

Page 31: ...31 1006905 ISSUE 2...

Page 32: ...Dantherm Ltd Unit 12 Galliford Road Maldon CM9 4XD United Kingdom 44 0 1621 856 611 sales uk dantherm com Calorex is a brand of danthermgroup co uk...

Reviews: